JKSSS+ Series - 50
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
SP.3 Phase & Ground Settings
(Setpoint Page 3)
(Security Level: 2)
MENU
PAGE 3  PHASE &
GROUND SETTINGS
IMBALANCE ALARM
LEVEL:   15% FLA
Range: 5 - 30%, OFF
Increments of 1
(Hit DOWN ARROW two times)
IMBALANCE ALARM
DELAY:        1.5 SEC.
Range: 1.0 - 20.0 SEC.
Increments of 0.1
IMBALANCE TRIP
LEVEL:  20%FLA
OVERCURRENT ALARM
LEVEL:   OFF
Range: 5 - 30%, OFF
Increments of 1
Range: 100 - 300%, OFF
Increments of 1
IMBALANCE TRIP
DELAY:   2.0 SEC.
OVERCURRENT ALARM
DELAY:   2.0 SEC.
Range: 1.0 - 20.0 SEC.
Increments of 0.1
Range: 1.0 - 20.0 SEC., OFF
Increments of 0.1
OVERCURRENT TRIP
LEVEL:  OFF
PHASE LOSS TRIP
:   ENABLED
Range: 100 - 300%, OFF
Increments of 1
Options: Enabled or Disabled
OVERCURRENT TRIP
DELAY:   2.0 SEC.
PHASE LOSS TRIP
DELAY:         0.1 SEC.
Range: 1.0 - 20.0 SEC.
Increments of 0.1
Range: 0 - 20.0 SEC.
Options:  ABC, ACB or
                Disabled
Range: 1.0 - 20.0 SEC.
Increments of 0.1
UNDERCURRENT ALARM
LEVEL:       OFF
Range: 10 - 90%, OFF
Increments of 1
UNDERCURRENT ALARM
DELAY:   2.0 SEC.
Range: 1.0 - 60.0 SEC.
Increments of 0.1
PHASE ROTATION
DETECTION:  ABC
GROUND FAULT LOSET
TRIP LEVEL:   OFF
Range: 5 - 90%, OFF
Increments of 1
PHASE ROTATION TRIP
DELAY: 1.0 SEC
 
GROUND FAULT LOSET
TRIP DELAY: 0.5 SEC
Range: 0.1 - 20.0 SEC.
Increments of 0.1
GROUND FAULT HISET
TRIP LEVEL:  OFF
Range: 5 - 90%, OFF
Increments of 1
GROUND FAULT HISET
TRIP DELAY:  0.008 SEC.
Range: 0.008 - 0.250 SEC.
Increments of 0.002
GROUND FAULT ALARM
LEVEL:  OFF
Range: 5 - 90%, OFF
Increments of 1
GROUND FAULT ALARM
DELAY:  0.1 SEC.
Range: 0.1 - 20.0 SEC.
Increments of 0.1
OVERVOLTAGE ALARM
LEVEL:     OFF
OVERVOLTAGE ALARM
DELAY:     1.0 SEC.
Range: 5 - 30%, OFF
Increments of 1
Range: 1.0 - 30.0 SEC.
Increments of 0.1
OVERVOLTAGE TRIP
LEVEL:     10%
OVERVOLTAGE TRIP
DELAY:     2.0 SEC.
Range: 5 - 30%, OFF
Increments of 1
Range: 1.0 - 30.0 SEC.
Increments of 0.1
UNDERVOLTAGE ALARM
LEVEL:     OFF
UNDERVOLTAGE ALARM
DELAY:     1.0 SEC.
Range: 5 - 30%, OFF
Increments of 1
Range: 1.0 - 30.0 SEC.
Increments of 0.1
UNDERVOLTAGE TRIP
LEVEL:     15%
UNDERVOLTAGE TRIP
DELAY:     2.0 SEC.
Range: 5 - 30%, OFF
Increments of 1
Range: 1.0 - 30.0 SEC.
Increments of 0.1
LINE FREQUENCY TRIP
WINDOW:     DISABLED
LINE FREQUENCY TRIP
DELAY:     1.0 SEC.
Range: 0 - 6, Disabled
Increments of 1
Range: 1.0 - 20.0 SEC.
Increments of 0.1
*
*
*
Note:  Proper phase sequence must be observed when 
connecting the input power. For example, phase A 
must lead phase B, which in turn must lead phase 
C by 120° respectively. If the phase rotation is 
not correct, a fault light and the LCD display will 
indicate the problem.
SP3.1 Imbalance Alarm Level: This is an advance warning 
of a phase imbalance problem. The problem may 
not be a fault in the motor, but merely caused by 
imbalanced voltages.
•  Imbalance Alarm Delay: The amount of time the 
imbalance condition must exist before an alarm 
occurs.
SP3.2 Imbalance Trip Level: This will trip the motor on 
excessive phase imbalance. The trip level should 
be programmed to a higher value than the alarm 
level.
•  Imbalance Trip Delay: The amount of time the 
imbalance condition must exist before a trip will 
occur.
SP3.3 Undercurrent Alarm Level: Typically used to warn 
of possible load loss, a coupling breaking or other 
mechanical problems.
•  Undercurrent Alarm Delay: The amount of time 
the undercurrent condition must exist before an 
alarm will occur.
SP3.4 Overcurrent Alarm Level: Typically used to indicate 
when the motor is overloaded. This feature can be 
used to either stop the feed to the equipment or 
warn operators of an overload condition.
•  Overcurrent Alarm Delay: The amount of time the 
overcurrent condition must exist before an alarm 
will occur.