Справочник Пользователя для Toshiba VF010H05

Скачать
Страница из 106
JKSSS+ Series - 51
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
SP.3 Phase & Ground Settings (Setpoint Page 3)
SP3.5 Overcurrent Trip Level: Typically used to indicate 
the motor is severely overloaded and at  which 
point a trip occurs.
•  Overcurrent Trip Delay: The amount of time the 
overcurrent condition must exist before a trip will 
occur.
SP3.6 Phase Loss 
Trip:  When 
enabled, the 
soft starter will 
trip the motor 
off-line upon a 
loss of
 
  phase power.
•  Phase Loss Trip Delay: The amount of time the 
phase loss condition must exist before a trip will 
occur.
SP3.7 Phase Rotation Detection: The soft starter is 
continuously monitoring the phase rotation. Upon 
a start command, a trip will occur if it detects a 
change in the phase rotation.
•  Phase Rotation: There are two possible phase 
rotation options: ABC or ACB. This setpoint 
monitors the wiring to ensure that the phase 
rotation is correct. To view the present phase 
rotation, go to Metering Page1, screen number 4.
SP3.8 * Ground Fault Alarm: Typically used to warn of low 
level ground current leakage.
•  * Ground Fault Alarm Delay:  The amount of  time 
that the ground fault condition must exist before an 
alarm will occur.
SP3.9 * Ground Fault Loset Trip Level: Typically used 
to trip the motor on a low level of ground current 
leakage. This setpoint is intended to detect high 
impedance faults. 
•  * Ground Fault Loset Trip Delay: The amount 
of time that the ground fault condition must exist 
before a trip will occur.
*Ground Fault Option must be installed
SP3.10  * Ground Fault Hiset Trip Level: Used to trip the 
motor (within milliseconds) upon detecting a high 
level of ground current leakage. This setpoint is 
intended to detect low impedance faults. 
•  *Ground Fault Hiset Trip Delay: The amount 
of time that the ground fault condition must exist 
before a trip will occur.
SP3.11  Overvoltage Alarm Level: Typically used to 
indicate when the line voltage is too high. This is 
an alarm level. 
•  Overvoltage Alarm Delay: The amount of time 
that the overvoltage condition must exist before a 
trip will occur.
MENU
PAGE 3  PHASE &
GROUND SETTINGS
POWER FACTOR LEAD
P/F ALARM:   OFF
Range: .01 - 1.00, OFF
Increments of .01
(Hit DOWN ARROW two times)
P/F LEAD ALARM
DELAY:        1 SEC.
Range: 1 - 120 SEC
Increments of 1
POWER FACTOR LEAD
P/F TRIP: OFF
POWER DEMAND
PERIOD:   10 MINUTES
Range: .01 - 1.00, OFF
Increments of .01
Range: 1 - 60 Minutes
Increments of 1
P/F LEAD TRIP
DELAY:   1.0 SEC.
Range: 1 - 120 SEC.
Increments of 1
KW DEMAND ALARM
PICKUP:  OFF KW
KVA DEMAND ALARM
PICKUP:  OFF KVA
Range: OFF, 1 - 100000
Increments of 1
Increments of 1
Increments of 1
Range: OFF, 1 - 100000
POWER FACTOR LAG
P/F TRIP:       OFF
Range:  .01 - 1.00, OFF
Increments of .01
P/F LAG TRIP
DELAY:   1.0 SEC.
Range: 1 - 120 SEC.
Increments of 1
KVAR DEMAND ALARM
PICKUP: OFF KVAR
Range: OFF, 1 - 100000
AMPS DEMAND ALARM
PICKUP: OFF AMPS
Range: OFF, 1 - 100000
Increments of 1
POWER FACTOR LAG
P/F ALARM:       OFF
Range:  .01 - 1.00, OFF
Increments of .01
P/F LAG ALARM
DELAY:   1.0 SEC.
Range: 1 - 120 SEC.
Increments of 1