Справочник Пользователя для Toshiba VF010H05

Скачать
Страница из 106
JKSSS+ Series - 52
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
SP3.12  Overvoltage Trip Level: Typically used to indicate 
that the line voltage is too high and at which point a 
trip occurs
•  Overvoltage Trip Delay: The amount of time that 
the overvoltage condition must exist before a trip 
will occur.
SP3.13  Undervoltage Alarm Level: Typically used to 
indicate when the line voltage is too low. This is an 
alarm level. 
•  Undervoltage Alarm Delay: The amount of time 
that the overvoltage condition must exist before a 
trip will occur.
SP3.14  Undervoltage Trip Level: Typically used to 
indicate that the line voltage is too low and at which 
point a trip occurs
•  Undervoltage Trip Delay: The amount of time that 
the undervoltage condition must exist before a trip 
will occur.
SP3.15  Line Frequency Trip Window: The acceptable 
amount of drift above or below the line frequency 
(Hz) before a trip is generated.
•  Line Frequency Trip Delay: The amount of time 
that the frequency drift condition must exist beyond 
the window before a trip will occur.
SP3.16  Power Factor Lead Alarm: Typically used to 
indicate a leading power factor. 
•  Power Factor Lead Alarm Delay: The amount of 
time that the power factor lead condition must exist 
beyond the window before a trip will occur.
SP3.17  Power Factor Lead Trip: The acceptable amount 
of power factor lead before a trip is generated.
•  Power Factor Lead Delay: The amount of time 
that the power factor lead condition must exist 
beyond the window before a trip will occur.
SP3.18  Power Factor Lag Alarm: Typically used to 
indicate a lagging power factor. 
•  Power Factor Lag Alarm Delay: The amount of 
time that the power factor lagging condition must 
exist beyond the window before a trip will occur.
SP3.19  Power Factor Lag Trip: The acceptable amount 
of power factor lag before a trip is generated.
•  Power Factor Lag Delay: The amount of time 
that the power factor lag condition must exist 
beyond the window before a trip will occur.
SP3.20  Power Demand Period: The soft starter 
measures the demand of the motor for several 
parameters (current, kW, kvar, kVA). The demand 
values of motors assists in energy management 
programs where processes may be altered or 
scheduled to reduce overall demand. Demand 
is calculated by a programmed amount of time 
where current, kW, kvar and kva samples are 
taken and then averaged and stored to assess 
demand.