Справочник Пользователя для Toshiba VF010H05

Скачать
Страница из 106
JKSSS+ Series - 55
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
SP.5 Relay Configuration (Setpoint Page 5)
(Security Level: 2)
In Setpoint Page 5 the user
can configure the four output
relays as either fail-safe or
non fail-safe and latching or
non-latching.
SP5.1 When a relay has been configured
 
as fail-safe and power is applied,
 
the relay will be energized. The
 
relay will then de-energize when
 
an event occurs or if the power
 
fails. Note: The relays in the 
 
soft starter will not prevent a start 
 
sequence unless they are wired in
 
as interlocks. If power is lost, the
 
motor power is also lost. Do not
 
change the programming for AUX
 
1-4. These are for factory use only.
 
AUX 5-8 are user defined outputs.
SP5.2 A relay configured as non-latching
 
will reset itself when the cause of
 
the trip event is not continuous. 
 
The TRIP (AUX1) relay should
 
always be programmed for latching,
 
because this trip should require a
 
visual inspection of the motor and
 
starter before issuing a manual
 
reset to release the relay after a trip
 
has been stored.
PAGE 5    RELAY
CONFIGURATION
TRIP (AUX1) RELAY
FAIL-SAFE:       NO
Options:  Yes or No
(Hit DOWN ARROW four times)
TRIP (AUX1) RELAY
LATCHED:        YES
ALARM (AUX2) RELAY
FAIL-SAFE:      NO
AUX4 RELAY
FAIL-SAFE:    NO
ALARM (AUX2) RELAY
LATCHED:     NO
AUX4 RELAY
LATCHED:     NO
AUX5 RELAY
FAIL-SAFE:     NO
AUX6 RELAY
FAIL-SAFE:     NO
AUX5 RELAY
LATCHED:     NO
AUX6 RELAY
LATCHED:     NO
AUX 3 RELAY
FAIL-SAFE:   NO
AUX3 RELAY
LATCHED:      NO
AUX7 RELAY
FAIL-SAFE:     NO
AUX7 RELAY
LATCHED:     NO
AUX8 RELAY
FAIL-SAFE:     NO
AUX8 RELAY
LATCHED:     NO
MENU