Справочник Пользователя для Toshiba VF010H05

Скачать
Страница из 106
JKSSS+ Series - 54
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
SP.4 Relay Assignment (Setpoint Page 4)
(Security Level: 2)
The protection functions are user programmable to an output relay. Factory setting for the trip functions assigned to TRIP 
(AUX1) relay and alarm functions to ALARM (AUX2) relay. AUX1 - 4 are Factory Set and should not be changed.
SP4.1  The following is a list of the user programmable functions. 
 
FUNCTIONS   
 
 
RELAy ASSIGNMENTS
 
 
 
 
 
 
1st  
 
 
2nd 
 
3rd
 
OVERLOAD TRIP 
 
 
TRIP ONLY 
 
NONE   
NONE
 
IMBALANCE TRIP 
 
 
TRIP (AUX1) 
 
NONE   
NONE
 
SHORT CIRCUIT TRIP   
 
TRIP ONLY 
 
NONE   
NONE
 
OVERCURRENT TRIP   
 
TRIP (AUX1) 
 
NONE   
NONE
 
STATOR RTD TRIP 
 
 
NONE   
 
NONE   
NONE
 
NON-STATOR RTD TRIP 
 
NONE   
 
NONE   
NONE
 
GROUND FAULT HI SET TRIP*   
TRIP (AUX1) 
 
NONE   
NONE
 
GROUND FAULT LO SET TRIP*  
TRIP (AUX1) 
 
NONE   
NONE
 
PHASE LOSS TRIP 
 
 
TRIP (AUX1) 
 
NONE   
NONE
 
ACCEL TIME TRIP 
 
 
TRIP ONLY 
 
NONE   
NONE
 
START CURVE TRIP   
 
TRIP ONLY 
 
NONE   
NONE
 
OVER FREQUENCY TRIP 
 
NONE   
 
NONE   
NONE
 
UNDER FREQUENCY TRIP 
 
TRIP (AUX1) 
 
NONE   
NONE
 
I*I*T START CURVE 
 
 
TRIP (AUX1) 
 
NONE   
NONE
 
LEARNED START CURVE 
 
TRIP (AUX1) 
 
NONE   
NONE
 
PHASE REVERSAL 
 
 
TRIP (AUX1) 
 
NONE   
NONE
 
OVERVOLTAGE TRIP   
 
TRIP (AUX1) 
 
NONE   
NONE
 
UNDERVOLTAGE TRIP  
 
TRIP (AUX1) 
 
NONE   
NONE
 
POWER FACTOR TRIP  
 
NONE   
 
NONE   
NONE
 
TACH ACCEL TRIP 
 
 
NONE   
 
NONE   
NONE
 
INHIBITS TRIP   
 
 
TRIP (AUX1) 
 
NONE   
NONE
 
SHNT TRIP 
 
 
 
NONE   
 
NONE   
NONE
 
BYPASS DISCREPANCY 
 
NONE   
 
NONE   
NONE
 
TCB FAULT 
 
 
 
TRIP (AUX1) 
 
NONE   
NONE
 
EXTERNAL INPUT 2 
 
 
NONE   
 
NONE   
NONE
 
DUAL RAMP   
 
 
NONE   
 
NONE   
NONE
 
THERMOSTAT   
 
 
TRIP (AUX1) 
 
NONE   
NONE
 
OVERLOAD WARNING  
 
ALARM (AUX2)   
NONE   
NONE
 
OVERCURRENT ALARM 
 
ALARM (AUX2)   
NONE   
NONE
 
SCR FAIL SHUNT ALARM 
 
ALARM (AUX2)   
NONE   
NONE
 
GROUND FAULT ALARM* 
 
ALARM (AUX2)   
NONE   
NONE
 
UNDERCURRENT ALARM 
 
NONE   
 
NONE   
NONE
 
MOTOR RUNNING 
 
 
AUX3   
 
NONE   
NONE
 
IMBALANCE ALARM   
 
ALARM (AUX2)   
NONE   
NONE
 
STATOR RTD ALARM   
 
NONE   
 
NONE   
NONE
 
NON-STATOR RTD ALARM 
 
NONE   
 
NONE   
NONE
 
RTD FAILURE ALARM   
 
NONE   
 
NONE   
NONE
 
SELF TEST FAIL 
 
 
TRIP (AUX1) 
 
NONE   
NONE
 
THERMAL REGISTER   
 
ALARM (AUX2)   
NONE   
NONE
 
U/V ALARM 
 
 
 
ALARM (AUX2)   
NONE   
NONE
 
O/V ALARM 
 
 
 
ALARM (AUX2)   
NONE   
NONE
 
POWER FACTOR ALARM 
 
NONE   
 
NONE   
NONE
 
KW DEMAND ALARM   
 
NONE   
 
NONE   
NONE
 
KVA DEMAND ALARM   
 
NONE   
 
NONE   
NONE
 
KVAR DEMAND ALARM  
 
NONE   
 
NONE   
NONE
 
AMPS DEMAND ALARM 
 
NONE   
 
NONE   
NONE
 
TIMED OUTPUT 
 
 
NONE   
 
NONE   
NONE
 
RUN DELAY TIME 
 
 
NONE   
 
NONE   
NONE
 
AT SPEED 
 
 
 
AUX4   
 
NONE   
NONE
*Ground fault option must be installed.