FX Series Programmable Controller
Diagnostic Devices 6
6-2
6.1
PLC Status (M8000 to M8009 and D8000 to D8009)
Diagnostic
Device
Operation
Diagnostic
Device
Operation
M8000 (
)
RUN monitor
NO contact
D8000 (
)
Watchdog
timer
FX, FX
2C
: 100ms
FX
0
, FX
0S
, FX
0N
, FX
2N
: 200ms
See note 1
M8001 (
)
RUN monitor
NC contact
D8001 (
)
PLC type and
version
20Vvv FX
0(S)
, FX
0N
, FX, FX
2C
version V.vv
24Vvv: FX
2N
 version V.vv
M8002 (
)
Initial pulse
NO contact
D8002 (
)
Memory
capacity
0002: 2K steps
0004: 4K steps
0008: 8K steps
(see also D8102)
M8003 (
)
Initial pulse
NC contact
D8003 (
)
Memory type
00H = RAM, 01H = EPROM,
02H = EEPROM,
0AH = EEPROM (protected)
10H = MPU memory
M8004 (
)
Error
occurrence
ON when one or more error 
flags from the range M8060 
to M8067 are ON
D8004 (
)
Error number
M
The contents of this register 
 identifies which error 
flag is active, i.e. if 
 = 
8060 identifies M8060
M8005
Battery
voltage Low
On when the battery voltage 
is below the value set in 
D8006
D8005
Battery
voltage
E.g. 36 = 3.6 volts
M8006
Battery error
latch
Latches the battery Low 
error
D8006
Low battery
voltage
The level at which a battery 
voltage low is detected
M8007
Momentary
power failure
D8007
Power failure
count
The number of time a momen-
tary power failure has occurred 
since power ON.
M8008
Power failure
Power loss has occurred 
D8008
Power failure
detection
The time period before shut 
down when a power failure 
occurs (default 10ms)
M8009
24V DC Down
Power failure of 24V DC 
service supply
D8009
24V DC
failed device
Lowest device affected by 24V 
DC power failure
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)
RUN
Input
M8061 error occurence
M8000
M8001
M8002
M8003
Program scan time
AC
Power
M8000
M8007
Approx. 5msec
Momentry power failure
M8008
Power failure
D8008
10msec
(Power failure
detection period)
For symbol key see page 6-1.
Note 1:
The contents of this register can be changed by the 
user. Settings in 1 msec steps are possible. The 
value should be set greater than the maximum scan 
time (D8012) to ensure constant scan operation.
General note:
When the power supply used is 200V AC, the power 
down detection period is determined by the value of 
D8008. This can be altered by the user within the 
allowable range of 10 to 100msec.