Справочник Пользователя для Mitsubishi Electronics FX2NC

Скачать
Страница из 382
FX Series Programmable Controller
Diagnostic Devices 6
6-3
6.2
Clock Devices (M8010 to M8019 and 
D8010 to D8019) 
For symbol key see page 6-1.
Note 2:
For FX
0
, FX
0S
 PLC’s and FX0N PLC’s not fitted with a RTC, the register D8013 
represents the value read from the first setting ‘pot’ in msec, range (0 to 255).
Diagnostic
Device
Operation
Diagnostic
Device
Operation
M8010
Reserved
D8010 (
)
Present scan
time
Current operation cycle / scan 
time in units of 0.1 msec
M8011 (
)
10 msec
clock pulse
Oscillates in 10 msec cycles
D8011 (
)
Minimum
scan time
Minimum cycle/ scan time in 
units of 0.1 msec
M8012 (
)
100 msec
clock pulse
Oscillates in 100 msec 
cycles
D8012 (
)
Maximum
scan time
Maximum cycle/ scan time in 
units of 0.1 msec
(waiting time for constant scan 
mode is not included)
M8013 (
)
1 sec
clock pulse
Oscillates in 1 sec cycles
M8014 (
)
1 min
clock pulse
Oscillates in 1 min cycles
The following devices apply to FX
2N(C)
 PLC’s and to FX
0N
, FX and FX
2C
 PLC’s when a 
real time clock cassette is installed.
D8013
Seconds
Seconds data for use with 
an RTC cassette (0 - 59)
(FX
0(S)
, FX
0N
 see note 2)
D8014
Minute data
Minute data for use with an 
RTC cassette (0-59)
M8015
Time setting
When ON - clock stops, ON 
 OFF restarts clock
D8015
Hour data
Hour data for use with an RTC 
cassette (0-23)
M8016
Register data
When ON D8013 to 19 are 
frozen but clock continues
D8016
Day data
Day data for use with an RTC 
cassette (1-31)
M8017
Min. rounding
When pulsed ON set RTC 
to nearest minute
D8017
Month data
Month data for use with an 
RTC cassette (1-12)
M8018 (
)
RTC available
When ON Real Time Clock 
is installed
D8018
Year data
Year data for use with an RTC 
cassette (0-99)
M8019
Setting error
Clock data has been set out 
of range
D8019
Weekday data
Weekday data for use with an 
RTC cassette (0-6)
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)