FX Series Programmable Controller
Diagnostic Devices 6
6-4
6.3
Operation Flags
For symbol key see page 6-1.
General note regarding input filters
The settings for input filters only apply to the main processing units which use 24V DC 
inputs. AC input filters are not adjustable.
Diagnostic
Device
Operation
Diagnostic
Device
Operation
M8020 (
)
Zero
Set when the result of an 
ADD (FNC 20) or SUB (FNC 
21) is “0”
D8020
(FX
0
/FX
0S
/
FX
0N
 only)
Input filter setting for devices 
X000 to X007 default is 10 
msec, (0-15)
M8021 (
)
Borrow
Set when the result of a SUB 
(FNC 21) is less than the 
min. negative number
D8020
(FX
2N(C)
 only)
Input filter setting for devices 
X000 to X017 default is 10 
msec, (0-15)
M8022 (
)
Carry
Set when ‘carry’ occurs dur-
ing an ADD (FNC 20) or 
when an overflow occurs as 
a result of a data shift opera-
tion
D8021
(FX
0
/FX
0S
 
only)
Input filter setting for devices 
X010 to X017 default is 10 
msec, (0-15)
M8023 (
)
Float
operation flag
(FX
2C
 only)
Set to enable floating point 
operations. This flag can be 
used with BCD, BIN, ADD, 
SUB, MUL,DIV, SQR and 
FLT applied instructions
D8022 -D8027
Reserved
M8024
Reserved
M8025
(Not FX
0(S)
FX
0N
)
When ON HSC (FNC 53 - 55) 
instructions are processed 
even when the external HSC 
reset input is activated
M8026
(Not FX
0(S)
FX
0N
)
RAMP (FNC 67) hold mode
M8027
(Not FX
0(S)
FX
0N
)
PR (FNC 77) 16 element 
data string
M8028
FX
0(S)
, FX
0N
: Change
timers T32 to T55 to 10ms 
type
FX, FX
2C
, FX
2N
: enable
interrupts during FROM/
TO
D8028 (
)
Current value of the Z index 
register
M8029 (
)
Instruction
execution
complete
Set on the completion of 
operations such as DSW 
(FNC 72), RAMP (FNC 67) 
etc.
D8029 (
)
Current value of the V index 
register
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)