Справочник Пользователя для Mitsubishi Electronics FX2NC

Скачать
Страница из 382
FX Series Programmable Controller
Diagnostic Devices 6
6-6
6.5
Step Ladder (STL) Flags 
(M8040 to M8049 and D8040 to D8049) 
For symbol key see page 6-1.
General note: 
All STL states are updated when the END instruction is executed.
Diagnostic
Device
Operation
Diagnostic
Device
Operation
M8040 (
)
STL transfer
disable
When ON STL state trans-
fer is disabled
D8040 (
)
Lowest active
STL step
Up to 8 active STL states, 
from the range S0 to S899, 
are stored in D8040 to D8047 
in ascending numerical order. 
(Updated at END)
M8041 (
S)
Transfer start
When ON STL transfer from 
initial state is enabled dur-
ing automatic operation
(ref. IST FNC 60)
D8041 (
)
2nd active
STL state
M8042 (
)
Start pulse
A pulse output is given in 
response to a start input
(ref. IST FNC 60)
D8042 (
)
3rd active
STL state
M8043 (
S)
Zero return
complete
On during the last state of 
ZERO RETURN mode
(ref. IST FNC 60)
D8043 (
)
4th active STL
state
M8044 (
S)
Zero point
condition
ON when the machine zero 
is detected
(ref. IST FNC 60)
D8044 (
)
5th active STL
state
M8045 (
)
All output
reset disable
Disables the ‘all output reset’ 
function when the operation 
mode is changed
(ref. IST FNC 60)
D8045 (
)
6th active STL
state
M8046 (
)
STL state ON
ON when STL monitoring 
has been enabled (M8047) 
and there is an active STL 
state
D8046 (
)
7th active STL
state
M8047 (
)
Enable STL
monitoring
When ON D8040 to D8047 
are enabled for active STL 
step monitoring
D8047 (
)
8th active STL
state
M8048 (
)
Annunciator
ON (Not FX
0(S)
FX
0N
)
ON when Annunciator moni-
toring has been enabled 
(M8049) and there is an 
active Annunciator flag
D8048
Reserved
M8049 (
)
Enable
Annunciator
monitoring
(Not FX
0(S)
FX
0N
)
When ON D8049 is enabled 
for active Annunciator state 
monitoring
D8049 (
)
Lowest active
Annunciator
(Not FX
0(S)
FX
0N
)
Stores the lowest currently 
active Annunciator from the 
range S900 to S999
(Updated at END)
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)