FX Series Programmable Controller
Diagnostic Devices 6
6-5
6.4
PLC Operation Mode
(M8030 to M8039 and D8030 to D8039) 
For symbol key see page 6-1.
Diagnostic
Device
Operation
Diagnostic
Device
Operation
M8030 (
)
Battery LED 
OFF
(Not FX
0(S
), 
FX
0N
)
Battery voltage is low but 
BATT.V LED not lit
D8030 (
)
(FX
0N
 only)
Value read from first setting 
“pot” in msec, (0 to 255)
M8031 (
)
Non-latch
memory all 
clear
Current device settings are 
reset at next END, i.e. con-
tacts, coils and current data 
values for Y, M, S, T, C and 
D devices respectively. Spe-
cial devices which have 
default settings are 
refreshed with those defaults
D8030
(Not FX
0(S)
FX
0N
)
This register is used as the 
3rd storage device when Z or 
V has been selected as the 
destination for the SPD 
instruction (FNC 56)
M8032 (
)
Latch memory
all clear
D8031 (
)
(FX
0N
 only)
Value read from second set-
ting “pot” in msec, (0 to 255)
M8033 (
)
Memory hold
in ‘stop’ mode
The device statuses and set-
tings are retained when the 
PLC changes from RUN to 
STOP and back into RUN
D8032 -D8038
Reserved
M8034 (
)
All outputs
disable
All of the physical switch 
gear for activating outputs is 
disabled. However, the pro-
gram still operates normally.
M8035 (
S)
Forced
operation
mode
By using forced operation 
mode, i.e.M8035 is turned 
ON, it is possible to perform 
remote RUN/STOP or 
pulsed RUN/ STOP opera-
tion.
Please see Chapter 10 for 
example operation
M8036 (
S)
Forced RUN
signal
M8037 (
S)
Forced STOP
signal
M8038(
)
RAM file
registers clear
(FX
(2C)
 only)
Used to clear the contents of 
the 2000 RAM file registers 
of any data
M8039 (
)
Constant
scan mode
When ON the PLC executes 
the user program within a 
constant scan duration. The 
difference between the 
actual end of the program 
operation and the set con-
stant scan duration causes 
the PLC to ‘pause’.
D8039 (
)
Constant
scan duration
This register can be written to 
by the user to define the dura-
tion of the constant scan. Res-
olutions of 1msec are 
possible.
This register has a default set-
ting 0 msec which will be initi-
ated during power ON.
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)