Справочник Пользователя для Mitsubishi Electronics FR-A700

Скачать
Страница из 523
254
Monitor display and monitor output signal
Frequency setting 
value
0.01Hz
5
5
Pr. 55
Display the set frequency.
Running speed
1(r/min)
6
6
The value 
converted 
with the Pr. 
37 value 
from Pr. 55
Display the motor speed
(The display differs depending on the Pr. 37 
and Pr. 144 settings. The running speed is the 
actual speed by the encoder signal during 
encoder feedback control and vector control. 
For details, refer to page 251.)
Motor torque 
0.1%
7
7
Pr. 866
Display the motor torque in percentage on the 
assumption that the rated motor torque is 100% 
(0% is displayed during V/F control)
Converter output 
voltage
0.1V
8
8
200V class:
400V
400V class:
800V
Display the DC bus voltage value.
Regenerative brake 
duty
0.1%
9
9
Pr. 70
Brake duty set in Pr. 30 and Pr. 70 
Electronic thermal 
relay function load 
factor
0.1%
10
10
100%
Display the motor thermal cumulative value 
on the assumption that the thermal operation 
level is 100%.
Output current 
peak value
0.01A/0.1A 
11
11
Pr. 56
Retain the peak value of the output current 
monitor and display (clears at every start)
Converter output 
voltage peak value
0.1V
12
12
200V class:
400V
400V class:
800V
Retain the peak value of the DC bus voltage 
value and display (clears at every start)
Input power
0.01kW/
0.1kW 
13
13
Rated 
inverter 
power 
× 
2
Display power on the inverter input side
Output power 
0.01kW/
0.1kW 
14
14
Rated 
inverter 
power 
× 
2
Display power on the inverter output side
Load meter
0.1%
17
17
Pr. 866
Torque current is displayed in % on the 
assumption that the Pr. 56 setting is 100%
(displayed on the assumption that rated 
motor torque is 100% during sensorless 
vector and vector control)
Motor excitation 
current
0.01A/0.1A  
18
18
Pr. 56
Display the excitation current of the motor
Position puls
19
×
Display the number of pulses per rotation of 
the motor when orientation control is valid (for 
FR-A7AP/FR-A7AL)
Cumulative 
energization time 
1h
20
×
Cumulative energization time since the 
inverter shipment is displayed.
You can check the numbers of the monitor 
value exceeded 65535h with Pr. 563.
Reference voltage 
output
21
Terminal FM:
1440 pulse/s is output when Pr. 291 = 0, 1.
50k pulse/s is output when Pr. 291 
 0, 1.
Terminal FM:
1440 pulse/s is output when Pr.291 = 0, 1.
50k pulse/s is output when Pr.291 
≠ 0, 1.
Terminal AM: 10V is output
Orientation status 
1
22
×
Display only when orientation control is valid  
(for FR-A7AP/FR-A7AL) (Refer to page 220)
Actual operation 
time 
1h
23
×
Cumulative inverter running time is displayed.
You can check the numbers of the monitor 
value exceeded 65535h with Pr. 564.
Use Pr. 171 to clear the value. (Refer to page 
Motor load factor
0.1%
24
24
200%
On the assumption that the rated inverter 
current value is 100%, the output current 
value is displayed in %.
Monitor value = output current monitor value/
rated inverter current 
×
 100 [%]
Cumulative power
0.01kWh/
0.1kW
25
×
Cumulative power amount is displayed 
according to the output power monitor.
Use Pr. 170 to clear the value. (Refer to page 
Torque command
0.1%
32
32
Pr. 866
Display torque command value obtained from 
vector control
Types of Monitor
Increments
Pr. 52 Setting
Pr. 54 (FM) 
Pr. 158 (AM)  
Setting
Full-scale 
Value of the 
Terminal FM 
and AM
Description
DU LED
PU main
monitor