4
*1
Frequency setting to output terminal status on the PU main monitor are selected by "other monitor selection" of the parameter unit (FR-PU04, FR-PU07).
*2
The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.
When the operation panel (FR-DU07) is used, the time is displayed up to 65.53 (65530h) in the indication of 1h = 0.001, and thereafter, it is added
up from 0.
*3
The actual operation time is not added up if the cumulative operation time before power supply-off is less than 1h.
*4
When using the parameter unit (FR-PU04/FR-PU07), "kW" is displayed.
*5
The setting depends on the inverter capacity. (55K or lower / 75K or higher)
*6
Since the panel display of the operation panel (FR-DU07) is 4 digits in length, the monitor value of more than "9999" is displayed as "----". 
*7
When the output current is less than the specified current level (5% of the rated inverter current), the output current is monitored as 0A. Therefore,
the monitored value of an output current and output power may be displayed as "0" when using a much smaller-capacity motor compared to the
inverter or in other instances that cause the output current to fall below the specified value.
*8
Available only when the plug-in option is mounted.
Torque current 
command
0.1%
33
33
Pr. 866
Display torque current command value
Motor output
0.01kW/
0.1k
34
34
Rated motor 
capacity
Multiply the motor speed by the then output 
torque and display the machine output of the 
motor shaft end
Feedback pulse
 
35
×
Display the number of pulses fed back from 
the encoder during one sampling (display 
during a stop). (for FR-A7AP/FR-A7AL)
The sampling time varies with the Pr.369 
Number of encoder pulses setting.
1050 or less: 1s
1051 to 2100: 0.5s
2101 to 4096: 0.25s
SSCNET III 
communication 
status 
1
39
×
Display the SSCNET III communication 
status. (for FR-A7NS)
Motor temperature 
1ºC
46
46
Pr. 751
Display the temperature of the vector control
dedicated motor with thermistor (SFV5RU
T/A)  (for FR-A7AZ)
Power saving effect
Variable 
according to 
parameters
50
50
Inverter 
capacity
Display energy saving effect monitor
You can change the monitor to power saving, 
power saving average value, charge display 
and % display using parameters.
(For details, refer to page 280.)
Cumulative saving 
power
51
×
PID set point
0.1%
52
52
100%
Display the set point, measured value and 
deviation during PID control (For details, refer 
to page 366)
PID measured 
value
0.1%
53
53
100%
PID deviation 
0.1%
54
×
Input terminal 
status
55
×
Display the input terminal ON/OFF status on 
the PU (refer to page 257 for DU display)
Output terminal 
status 
×
Display the output terminal ON/OFF status 
on the PU (refer to page 257 for DU display)
Option input 
terminal status  
56
×
×
Display the input terminal ON/OFF status of 
the digital input option (FR-A7AX) on the DU 
(refer to page 257 for details)
Option output 
terminal status 
57
×
×
Display the output terminal ON/OFF states of 
the digital output option (FR-A7AY) or relay 
output option (FR-A7AR) on the DU (refer to 
page 257 for details)
Types of Monitor
Increments
Pr. 52 Setting
Pr. 54 (FM) 
Pr. 158 (AM)  
Setting
Full-scale 
Value of the 
Terminal FM 
and AM
Description
DU LED
PU main
monitor