7000 Bus Converter User Manual (version 1.2,Feb/2003, 7PH-006-10)  --------------- 79 
6.4    RS-232 Devices Network 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Some RS-232 devices can be connected to the 7000 RS-485 
network very easily, just like the PC or PLC introduced in Sec 2.7 and Sec. 
2.8. These RS-232 devices must adhere to 3 rules given as follows: 
 
Rule 1: cannot send out the RS-232 signal in normal, 
operating state. 
Rule 2: every device has a unique device address 
Rule 3: will not send out a RS-232 signal if the destination 
address does not match with the device address 
 
 
The software for RS-232 device networking and PLC 
networking is very similar. The only difference is the command 
format. The command format of PLC is always different for 
different manufacturers. Refer to “NAP000S User Manual” for 
software details. 
 
 
RS-232 
 
RS-485
PWR-24
Connecting 256 RS-232
devices max. Without a
repeater, the 7510 
7520 
7520 
 
7000 series 
 
Host PC
 
RS-232 
7520 
RS-232 
RS-232 device 
Fig 34
 
RS-232 device