7000 Bus Converter User Manual (version 1.2,Feb/2003, 7PH-006-10)  --------------- 81 
7.2    Changing Module Address 
 
Wire connection: Refer to Sec. 2.7 
Test program: Refer to “NAP7000S User Manual” for TEST.EXE 
 
 
The steps to change module address are given as follows. 
1.  Wire connection, power on and run test.exe 
2. Press 2 
3. Press $012[Enter] 
 Receive=! 01080600 
4. Press 2 
5. Press %0102080600[Enter]
 Receive=! 02 
6. Press 2 
7. Press $022[Enter] 
 Receive=! 02080600 
8. Press 2 
9. Press $02M[Enter] 
 Receive=! 027017 
10. Press 2 
11. Press $02F[Enter] 
 Receive=! 02A1.3 
 
  Step 3: read the module status and find that module address=01, baud rate= 
9600, checksum is enable. 
  Step 5: change the module address from 01 to 02, the module address can 
be changed immediately, no need to power-off then power-on 
  Step 7: read the module status based on the module address=02 
  Step 9: read the module name 
 
Step 11: read the firmware number of this module
 
 
 
 
NOTE:
 If the user uses $AA2 command to change module configuration, the 
new configuration code will be stored into EEPROM immediately. The 
configuration code includes module address, module type, baud rate 
code, checksum enable/disable code, calibration code, power-on value 
and safe value. The EEPROM data of the 7000 series can be read an 
infinite number or times and can be written about 100,000 times max. 
Therefore the user should not change the configuration code often when 
testing.