7.    Quick Starting the 7000 Series 
7.1    Find Status of Unknown Module 
 
Wire connection: Refer to Sec. 2.7
 
Test program: Refer to “NAP7000S User Manual” for TEST.EXE 
 
Connect I NIT*_pin to GND_pin first as follows. 
 
 
The steps to finding the status of an unknown module are given as follows. 
1. Wire 
connection, 
INIT*_pin=GND, power on and run test.exe 
2. Press 2 
3. Press 
$002[Enter] 
 Receive=! 02080A40 
4. Press 
2 
5. Press 
%0001080600[Enter]
 Receive=! 01 
6.  Power off, disconnect INIT*_pin (pin 6) and GND_pin (pin_10) and power on 
7. Press 
2 
8. Press 
$012[Enter] 
 Receive=! 01080600 
9. Press 
2 
10. Press $01M[Enter] 
 Receive=! 017017 
11. Press 2 
12. Press $01F[Enter] 
 Receive=! 01A1.3 
 Step 3: read the module status with the INIT*_pin connected to the 
GND_pin and find that module address=02, baud rate= 115200, checksum 
is enable. 
 Step 5: change this module to address=01, baud rate=9600, checksum 
disable 
 
Step 6-12: disconnect the INIT*_pin and read back the module status
 
 
NOTE:
 If the INIT*-pin is connected to GND-pin, the 7xxx will go to its 
default setting as follows:  
(1) Module address=00; (2) baud rate=9600; (3) checksum is disable