Jump response to various control deviations  
(open control circuit, actuator removed) 
Adjustment time T
n
 = 7 min. 
Sample time T
n
 = 20 sec. 
Mixed heating circuit runtime = 2 min. 
The P-pulse that brings the mixed heating circuit to the new 
position and is proportional to the control deviation is followed by 
additional actuation pulses if the control deviation is not yet 
remedied (I-part). The adjustment time remains constant despite 
varying control deviations. 
 
7.3.4.10.1.5 Actuator 
end position function 
This function determines the type of control signal in the end 
positions OPEN or CLOSED of each actuator. 
1 = Continuous voltage at connection OPEN or CLOSED at the 
respective end position 
2 = De-energised at end position OPEN or CLOSED respectively 
Recommendation for the basic setting of the adjustment time with 
different heating systems: