Hydraulic Components 
SDC / DHC  
188 EN2H-0221GE51 
R0808 
Hot-water economy temperature is the setpoint for the hot-water 
tank between the active operating mode times in automatic mode. 
If a hot-water thermostat is used to determine the water heater 
temperature, the parameter for the setting of the economy 
temperature is skipped.  
 
In order to kill Legionella germs in the tank, a Legionella 
protection function can be activated. Activation is carried out in 
the "Hot Water" menu, parameter 2. 
To ensure full destruction of germs, the set value of the Legionella 
protection temperature must be at least 65°C. 
The setting is carried out with two parameters. The weekday for 
Legionella protection can be selected by the user with a freely 
accessible parameter. With parameters 03 and 04, the time and 
temperature can be set by the heating technician.  
 
Type of temperature measurement  
This function determines the type of temperature measurement in 
the hot-water tank. 
In general, an electronic temperature sensor (immersion sensor in 
hot-water tank) is used. The temperature is measured via the 
change in resistance of this sensor here. 
Alternatively, hot water provision can also be controlled by a 
mechanical temperature controller (thermostat switching contact). 
A hot-water thermostat is connected to tank sensor input and set 
to the required setpoint hot-water temperature. When the 
thermostat requires energy via the tank sensor input (contact 
closed), the tank is loaded with hot water at the set hot water 
maximum temperature until the contact opens again. 
 
With hot water control through a thermostat, the current hot water 
temperature cannot be measured and registered and will 
therefore not be displayed as part of the system information. Also, 
the hot water nominal temperatures cannot be set. 
 
This function limits the temperature in the water heater upward 
based on the set value. The desired water heater daytime 
temperature to be set on the user level is limited by this set value.  
 
Hot-water circuit - night-
time 
Legionella protection 
Temperature 
measurement 
NOTE
Maximum hot water 
temperature