Honeywell EN2H-0221GE51 R0808 用户手册

下载
页码 258
SDC / DHC 
Hydraulic Components 
EN2H-0221GE51 R0808 
187 
7.3.5 Hot-water 
production 
 
7.3.5.1  Hot-water tank loading (SLP)  
The output controls a hot-water circuit loading pump during the 
respective operational-readiness times upon demand. 
 
The hot-water daytime temperature provides for the desired hot 
water temperature during hot-water circuit operational-readiness 
times in automatic mode and in the PARTY and HEATING control 
modes. 
This set value is the initial value for the temperature specifications 
that can be set for each heating cycle in the switching-time 
programs. The temperature settings in the switching time 
programs are automatically adjusted when the hot-water daytime 
temperature is changed. 
 
Example: Before 
Daytime hot-water temperature value: 50°C 
 
Temperatures in switching-time program: 
05:00 hours –  08:00 hours 
60°C 
08:00 hours –  16:00 hours 
50°C 
16:00 hours –  22:00 hours 
60°C 
 
Example: After  
Daytime hot-water temperature value: 52 °C 
 
Temperatures in switching-time program: 
05:00 hours –  08:00 hours 
62°C 
08:00 hours –  16:00 hours 
52°C 
16:00 hours –  22:00 hours 
62°C 
 
Changed settings are stored when key 
§
 or 
î
 is briefly pressed 
again or after automatic return at a preset time. Once the settings 
are stored, the unit automatically switches to the basic display. 
 
5.1.2.4 "Daytime hot-water temperature" button, pg. 25 
 
Function
Hot-water circuit - 
daytime 
See also