SDC / DHC 
Hydraulic Components 
EN2H-0221GE51 R0808 
189 
 ATTENTION 
Hot water maximum temperature limit is a function protecting 
the tank and terminates hot water loading. If overshooting 
occurs, the tank loading pump switches off immediately. In 
this case it cannot be ensured that the set extended running 
time is adhered to. 
 
If a hot-water circuit thermostat is used instead of an electronic 
sensor, the hot water maximum temperature setting (plus the 
specified temperature shift during loading) is forwarded to the 
heat generator. 
 
With this function it is set how the rest of the heating system 
reacts to heat demand from the hot-water tank. There are 5 
different setting options.  
 
Parallel operation  
During hot-water circuit loading, the heating circuits remain 
operative. 
 
Priority mode  
During hot-water loading, the heating circuits are put out of 
operation. They are restarted as soon as the hot-water circuit 
loading pump extended running time is over. 
If the hot-water setpoint temperature is not reached after 4 hours, 
a fault message is indicated on the display. 
 
Conditional priority  
If the temperature of the heat generator has exceeded the loading 
temperature for the hot-water tank, mixed heating circuits are 
enabled. Non-mixed heating circuits (DHCP) remain disabled 
during hot-water circuit loading. The heating circuits are enabled 
according to the following criteria: 
 
Enabling the heating circuits: 
Heat generator actual temperature > hot-water setpoint 
temperature + hot-water switching differential/2 + 10 K 
 
Disabling the heating circuits: 
Heat generator actual temperature < hot-water setpoint 
temperature + hot-water switching differential/2 + 5 K 
NOTE
Control mode