cx400/px400 Sub. pump • operation and partS manual — rev. #1 (12/03/10) — page 23
Maintenance
electrical insulation testing
Why perform electrical insulation testing? 
Electrical insulation starts to age as soon as it's made.  
Harsh  environments,  especially  those  with  extreme 
temperature  changes  and/or  chemical  contamination, 
cause further deterioration of the insulation (power cord).
As  a  result,  personnel  safety  (electrocution/shock)  and 
power  reliability  can  suffer  resulting  in  higher  operating 
cost and maintenance.
What is Insulation Resistance Testing
Insulation resistance testing applies a regulated stabilized 
high  voltage  (Figure  22),  typically  500 VDC  or  greater 
across a dielectric (power cord). Measuring the amount of 
leakage current flowing through the dielectric will yeild a 
resistive measurement in megohms.
Insulating Material Testing
To  verify  the  integrity  of  the  pump's  insulating  material 
(power cable) it will be necessary to perform an electrical 
insulation  test.  Any  electrical  insulation  must  have  the 
opposite characteristic as the conductor: it should resist 
the flow of current, keeping it within the conductor.
To measure the IR (current x resistance), the use of an IR 
tester must be employed. This IR tester is a portable device 
that is a resistance meter (ohmmeter) with a built in DC 
generator that develops a high DC voltage.
The high DC voltage from the IR tester is usually 500 VDC 
or more. This voltage, when applied causes a small current 
to flow through and over the insulation's surfaces. The tester 
provides a direct reading of IR in megohms.
A  high  resistance  reading  would  indicate  a  "
good
insulation, meaning very little current is escaping through 
the  insulation. While  a  relatively  low  resistance  reading 
would  indicate 
poor  insulation,  meaning  a  significant 
amount of current may be leaking through and along the 
insulation.
Figure 22. Insulation Tester Application
NOTICE
Insulation  resistance  is  moisture  and  temperature 
sensitive. When  temperature  increases,  insulation 
resistance decreases, and vice versa.
When performing this test measurement, perfom the 
test using the same test parameters as used in the 
initial testing.
V
OFF
20M
MEGGER™
SET
UP
M
K
GROUND
PIN
POWER CABLE
INSULATION
500 VDC INSULATION
TEST METER
SUBMERSIBLE
PUMP
PX400
  danger
Read and follow the manufacturer's users 
manual prior to operating insulation tester 
(megaohm meter). This meter generates 
a test voltage of 500 volts or greater. Only 
qualified  and  trained  personnel  should 
use  this  equipment. The  possibility  exists  of  severe 
electrical shock, electrocution even death!, when 
using insulation tester.