dca220sscu/4i 60 hz generaTor• operaTion manual — rev. #0 (10/25/12) — page 21
OUtpUt terMiNaL paNeL faMiLiariZatiON
120 vac gFci receptacles
There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-20R) 
receptacles provided on the output terminal panel. These 
receptacles can be accessed in any
 voltage change-over 
board configuration. Each receptacle is protected by a 20 
amp circuit breaker. These breakers are located directly 
above the GFCI receptacles. Remember the load output 
(current) of both GFCI receptacles is dependent on the 
load requirements of the U, V, and W output terminal lugs.
Pressing the 
reset button resets the GFCI receptacle after 
being tripped. Pressing the 
test button (See Figure 7) in 
the center of the receptacle will check the GFCI function. 
Both receptacles should be tested at least once a month.
Figure 7. G.F.C.I. Receptacle
Twist lock dual voltage 120/240 vac receptacles
There are three 240/139V, 50 amp auxiliary twist-lock (CS-
6369)  receptacles  (Figure  8)  provided  on  the  output 
terminal panel. These receptacles can 
only be accessed 
when  the  voltage  change-over  board  is  configured  for  
single-phase 240/120 application
Figure 8. 240/139V Twist-Lock Auxiliary 
Receptacles
Each auxiliary receptacle is protected by a 50 amp circuit 
breaker. These  breakers  are  located  directly  above  the 
GFCI receptacles. Remember the load output (current) on 
all three receptacles is dependent on the load requirements 
of the 
output terminal lugs.
Turn the 
voltage regulator control knob (Figure 9) on the 
control panel to obtain the desired voltage. Turning the knob 
clockwise  will 
increase  the  voltage,  turning  the  knob 
counter-clockwise will 
decrease the voltage.
Figure 9. Voltage Regulator Control Knob