page 22 — dca220sscu/4i 60 hz generaTor • operaTion and parTs manual — rev. #0 (10/25/12) 
OUtpUt terMiNaL paNeL faMiLiariZatiON
connecting loads
Loads can be connected to the generator by the 
output 
Terminal lugs or the convenience receptacles (Figure 10). 
Make sure to read the operation manual before attempting 
to connect a load to the generator.
To protect the output terminals from overload, a 3-pole, 
600A 
main circuit breaker is provided. Make sure to switch 
all circuit breakers to the oFF position prior to starting 
the engine.
Figure 10. Connecting Loads
over current relay
An 
over current relay (Figure 11) is connected to the main 
circuit breaker. In the event of an overload, both the circuit 
breaker and the over current relay may trip. If the circuit 
breaker can not be reset, the 
reset button on the over 
current relay must be pressed. The over current relay is 
located in the control box.
Figure 11. Over Current Relay
NOTICE
Remember the
 overcurrent relay monitors the current 
flowing from the 
u,v, and W output Terminal lugs 
to the load.
In the event of a short circuit or over current condition, 
it will automatically trip the 600 amp main breaker.
To restore power to the 
output Terminal panel, press 
the reset button on the overcurrent relay and place the 
main circuit breaker in the closed position (on).