Error 
Code 
Name 
Cause(s) 
E25 
Main circuit 
error (*3) 
The inverter will trip if the power supply establishment is 
not recognized because of a malfunction due to noise or 
damage to the main circuit element. 
E30
 
Driver error 
An internal inverter error has occurred at the safety 
protection circuit between the CPU and main driver unit. 
Excessive electrical noise may be the cause. The inverter 
has turned OFF the IGBT module output. 
E35
 
Thermistor 
When a thermistor is connected to terminals [5] and [L] 
and the inverter has sensed the temperature is too high, 
the inverter trips and turns OFF the output. 
E36 
Braking error 
When "01" has been specified for the Brake Control 
Enable (b120), the inverter will trip if it cannot receive the 
braking confirmation signal within the 
Brake Wait Time for Confirmation (b124) after the output 
of the brake release signal. 
E37 
Safe Stop 
Safe stop signal is given. 
E38 
Low-speed overload protection 
If overload occurs during the motor operation at a very low 
speed, the inverter will detect the 
overload and shut off the inverter output. 
E40
 
Operator connection 
When the connection between inverter and operator 
keypad failed, inverter trips and displays the error code. 
E41
 
Modbus communication error 
When “trip” is selected (C076=00) as a behavior in case of 
communication error, inverter trips when timeout happens. 
E43
 
EzSQ invalid instruction 
The program stored in inverter memory has been 
destroyed, or the PRG terminal was turned on without a 
program downloaded to the inverter. 
E44
 
EzSQ    nesting count error 
Subroutines, if-statement, or for-next loop are nested in 
more than eight layers 
E45
 
EzSQ instruction error 
Inverter found the command which cannot be executed. 
E50 
to 
E59
 
EzSQ user trip (0 to 9) 
When user –defined trip happens, inverter trips and 
displays the error code.   
E60
 
Option error (DeviceNet 
Communications error) 
If the disconnection due to the Bus-Off signal or timeout 
occurs during the operation using DeviceNet commands, 
the inverter will shut off its output and display the error 
code shown on the right. 
(The inverter will trip according to the settings of "P045" 
and "P048".) 
E61 
Option error (duplicated MACID)   
If two or more devices having the same 
MAC ID are detected in the same network, the inverter will 
display the error code shown on the right. 
E62 
Option error (External trip) 
If the Force Fault/Trip bit of Attribute 17 in the Instance 1 
of the Control Supervisory object is set to "1", the inverter 
will shut off its output and display the error code shown on 
the right. 
E63 
 to 
E68 
Option error   
The inverter detects errors in the option board mounted in 
the optional slot. For details, refer to the instruction 
manual for the mounted option board. 
E69 
Option error (inverter communication 
error) 
If timeout occurs during the communication between the 
inverter and DeviceNet option board, the inverter will shut 
off its output and display the error code shown on the 
right. 
E80 
Encoder 
disconnection 
If the encoder wiring is disconnected, an encoder 
connection error is detected, the encoder fails, or an 
encoder that does not support line driver output is used, 
the inverter will shut off its output and display the error 
code shown on the right.