Hitachi hitachi series inverter 用户手册

下载
页码 99
 
87 
Error 
Code 
Name 
Cause(s) 
E81 
Excessive speed 
If the motor speed rises to "maximum frequency 
(A004) x over-speed error detection level (P026)" or more, 
the inverter will shut off its output and display the error 
code shown on the right. 
E83 
Positioning 
range 
error 
If current position exceeds the position range 
(P072-P073), the inverter will shut off its output and 
display the error code. 
 
Other indication 
 
Error 
Code 
Name 
Descriptions 
                Rotating
 
Reset 
RS input is ON or STOP/RESET key is pressed. 
 
Undervoltage 
If input voltage is under the allowed level, inverter shuts 
off output and wait with this indication. 
 
Waiting to restart 
This indication is displayed after tripping before 
restarting. 
 
Restricted operation 
command 
Commanded RUN direction is restricted in b035. 
 
Trip history initializing  Trip history is being initialized. 
 
No data 
(Trip monitor) 
No trip/waning data exists. 
              Blinking
 
Communication error 
Communication between inverter and digital operator 
fails. 
 
Auto-tuning 
completed 
Auto-tuning is completed properly. 
 
Auto-tuning error 
Auto-tuning fails. 
 
NOTE
Reset is not allowed in 10 second after trip. 
NOTE
When error E08, E14 and E30 occur, reset operation by RS terminal or STOP/RESET key is 
not accepted. In this case, reset by cycling power. If still same error occurs, perform initialization. 
 
Restoring Factory Default Settings 
You can restore all inverter parameters to the original factory (default) settings according to 
area of use. After initializing the inverter, use the powerup test in Chapter 2 to get the 
motor running again. If operation mode (std. or high frequency) mode is changed, inverter 
must be initialized to activate new mode. To initialize the inverter, follow the steps below. 
 
(1) Select initialization mode in 
b084
(2) If 
b084
=
02
03
 or 
04
, select initialization target data in 
b094
(3) If 
b084
=
02
03
 or 
04
, select country code in 
b085
(4) Set 
01
 in 
b180
.  
(5) The following display appears for a few seconds, and initialization is completed with
 
d001
 
displayed.
 
* Please change from"
0 4
 (Basic display)" to "
0 0
 (Full display)" in parameter 
                     
B 0 3 7
 (Function code display restriction), in case some parameters cannot be displayed.