  CE-EMC Installation Guidelines 
You are required to satisfy the EMC directive (2004/108/EC) when using an WJ200 inverter in an 
EU country. 
To satisfy the EMC directive and to comply with standard, you need to use a dedicated EMC filter 
suitable for each model, and follow the guidelines in this section. Following table shows the 
compliance condition for reference. 
Table 1. Condition for the compliance 
Model 
Cat. 
Carrier f 
Motor cable 
All WJ200 series 
C1 
2kHz 
20m  (Shielded) 
Table 2. Applicable EMC filter 
Input class 
Inverter model Filter model (Schaffner) 
WJ200-001SF
WJ200-002SF
WJ200-004SF
FS24828-8-07 
WJ200-007SF
WJ200-015SF
1-ph. 200V class 
WJ200-022SF
FS24828-27-07 
WJ200-001LF
WJ200-002LF
WJ200-004LF
WJ200-007LF
FS24829-8-07 
WJ200-015LF
WJ200-022LF
FS24829-16-07 
WJ200-037LF
FS24829-25-07 
WJ200-055LF
WJ200-075LF
FS24829-50-07 
WJ200-110LF
FS24829-70-07 
3-ph. 200V class 
WJ200-150LF
FS24829-75-07 
WJ200-004HF
WJ200-007HF
FS24830-6-07 
WJ200-015HF
WJ200-022HF
WJ200-030HF
FS24830-12-07 
WJ200-040HF FS24830-15-07 
WJ200-055HF
WJ200-075HF
FS24830-29-07 
WJ200-110HF
3-ph. 400V class 
WJ200-150HF
FS24830-48-07 
WJ200-110L and 150H needs to be installed in a metal cabinet and add ferrite core at 
the input cable to meet category C1. Unless otherwise category C2. 
 
Important notes 
1.  Input choke or other equipment is required if necessary to comply with EMC directive 
from the harmonic distortion point of view (IEC 61000-3-2 and 4). 
2.  If the motor cable length exceeds 20m, use output choke to avoid unexpected problem 
due to the leakage current from the motor cable (such as malfunction of the thermal 
relay, vibration of the motor, etc..). 
3.  As user you must ensure that the HF (high frequency) impedance between adjustable 
frequency inverter, filter, and ground is as small as possible.