Extension cords 
The use of an extension cord is not 
recommended for the PJ882 Jointer. But if one 
is necessary, make sure the cord rating is 
suitable for the amperage listed on the 
machine’s motor plate. An undersized cord will 
cause a drop in line voltage resulting in loss of 
power and overheating. 
Use the chart in Figure 8 as a general guide in 
choosing the correct size cord. If in doubt, use 
the next heavier gauge. The smaller the gauge 
number, the heavier the cord. 
230 Volt, Single Phase Operation 
As received from the factory, the single-phase 
model of the PJ-882 Jointer is designed to run 
on 230 volt power only. 
The jointer has a grounding plug that looks like 
the plug illustrated in Figure 9; or you may 
choose to “hard-wire” the machine directly to a 
control panel. If hard-wired to a panel, make 
sure a disconnect is available for the operator. 
The Jointer must comply with all local and 
national codes after being wired. 
If the Jointer is to be hard-wired, make sure the 
fuses have been removed or the breakers have 
been tripped in the circuit to which the Jointer 
will be connected. Place a warning placard on 
the fuse holder/circuit breaker to prevent it being 
turned on while the machine is being wired. 
The Jointer with a 230 volt plug should only be 
connected to an outlet having the same 
configuration. No adapter is available or should 
be used with the 230 volt plug. 
It is recommended that the single phase jointer 
be connected to a dedicated, minimum 20 amp 
circuit with a 20 amp circuit breaker or time 
delay fuse. Local codes take precedence over 
recommendations.  
Three Phase Operation 
The three-phase model is factory wired for 230 
volt, but can be converted to 460 volt if so 
desired (see “Converting From 230 Volt to 460 
Volt”). 
“Hard-wire” the machine directly to a control 
panel and make sure a disconnect is available 
for the operator.  
If you are hard-wiring the Jointer, make sure the 
fuses have been removed or the breakers have 
been tripped in the circuit to which the Jointer 
will be connected, and place a warning placard 
on the fuse holder or circuit breaker to prevent it 
being turned on until wiring is complete. 
Recommended Gauges (AWG) of Extension Cords
Amps 
Extension Cord Length * 
25 
feet 
50 
feet 
75 
feet 
100 
feet 
150 
feet 
200 
feet 
16 16 16 14 12 12 
to 
8  16 16 14 12 10 NR 
to 
12  14 14 12 10 NR NR 
12 
to 
15 12 12 10 10 NR NR 
15 to 20 
10 
10 
10 
NR 
NR 
NR 
21 
to 
30  10  NR NR NR NR NR 
*based on limiting the line voltage drop to 5V at 150% of the 
rated amperes. 
NR: Not Recommended.
 
Figure 8 
 
Figure 9 
 
It is recommended that the three phase jointer, 
when operated at 230 volts, be connected to a 
dedicated,  minimum  20 amp circuit with a 20 
amp circuit breaker or time delay fuse. When 
operated at 460 volts, connect the jointer to a 
dedicated, minimum 15 amp circuit with 15 amp 
circuit breaker or time delay fuse. Local codes 
take precedence over recommendations. 
Converting from 230 Volt to 460 Volt 
(Three Phase Only) 
Consult the wiring diagram inside the starter box 
cover. A diagram is also included on page 46 of 
this manual. The Jointer must comply with all 
local and national codes after being wired. 
1.  Replace the current contactor with the 460V 
magnetic contactor (part no. PJ882-526C; 
purchased separately). 
2.  Re-connect the incoming leads to the motor 
for 460 volt operation, as shown in the wiring 
diagram. 
3.  If using a plug, install a proper UL/CSA listed 
plug suitable for 460 volt operation.