Chapter 3
Tag Configuration
3-34
© National Instruments Corporation
How Do You Configure Alarms for a Tag?
While editing a tag, click the Enable Alarms checkbox. Alarms are 
generated depending on the value or state of a tag. The alarms based on 
value vary with the tag data type. But for any tag, if the status is bad, a 
Bad Status alarm is generated. By default, Bad Status Alarm is enabled 
and has the highest priority (15). You can change this selection from the 
Alarms tab of the Tag Configuration Editor, shown in Figure 3-11.
Analog Tags
Analog tags have four alarm levels: HI_HI, HI, LO, and LO_LO. By 
providing separate alarm levels, you can provide more information about 
the nature of the alarm condition.
 
Figure 3-11.  Alarms for Analog Tag Configuration
Alarms are calculated after scaling is performed. Alarm levels are 
expressed in engineering units.