Figure 3-13.  Alarms for Bit Array Tag Configuration
String Tags
String tags have no alarm states based on tag value. They only support 
Bad Status alarms.
What Is Alarm Deadband on Analog Tags?
Alarm Deadband is a method commonly used to avoid repetitive alarm 
messages because of a tag value that hovers near the alarm limit. Alarm 
Deadband defines how much a tag value must change from the alarm 
limit before it is considered normal. For example, if a tag that represents a 
temperature value hovers near an alarm limit of 40 degrees Celsius, the tag 
might go in and out of alarm many times in a relatively short period of time. 
Table 3-8 shows examples of events with Alarm Deadband set to 0.0%.
 
Table 3-8.  Events with Alarm Deadband = 0.0%
Time
Value
Event
Alarm Type
9:15:05
40.1
Yes
 HI 
9:15:10
39.9
Yes
 Normal