Installing and Cabling the Cabinets
46 Installation, Upgrades and Additions for Avaya CMC1 Media Gateways
Connect Cabinet Grounds and Other Grounds
The following additional grounding requirements must be met:
●
The approved ground wire must be green, 6 AWG (#40) (16 mm
2
), copper, stranded wire
(this is in addition to the ground wire in the AC power cord)
●
Bond all approved grounds at the single-point ground to form a single grounding electrode
system
system
Install the Ground Block
To install the ground block
2. Make the cable connections as shown in
.
Figure 10: Ground Block Installation to Right Panel
Figure notes:
1. #12 x 1-inch shoulder screws
2. Single-point ground block
indmingb RPY 012398
1
2
2
A