Operation
12
Three-Phase Rack PDU — Installation and Operation Manual
Alarm conditions
You configure warning and alarm limits through the internal menus, 
using a serial port connection. 
The Rack PDU shows warning and alarm conditions as follows:
Phase Indicator LED 
Displays yellow for a warning and red for an 
alarm.
Digital Display
If one phase is at or above the warning or 
alarm limit, the display shows the current for 
that phase. 
If more than one phase is at or above the 
warning or alarm limit, the display cycles 
among those phases, displaying their current.
Control Button
Pressing this button causes the digital display 
to display the current for the next phase for 30 
seconds. Then it returns to the display of the 
current for any phases that are at or above the 
warning or alarm limits.
Warning
Do not exceed the maximum voltage and 
current ratings listed on the rear panel of 
the Rack PDU.