Three-Phase Rack PDU — Installation and Operation Manual
13
Wiring Options
Hardwiring procedure 
(optional)
Remove the power cord. 
1. Detach the inspection cover on the power inlet end of the Rack 
PDU by removing the four screws on the sides of the cover and 
tilting the cover upward so that the terminal block is exposed. Set 
the screws aside for later use.
2. Loosen the four screws that hold the power cord’s wires to the 
terminal block, and loosen the screw that holds the ground wire to 
the standoff on the metal chassis.
3. Pull the power cord and the inspection cover from the Rack PDU. 
Attach wiring to terminal block. 
4. Attach a 1-inch conduit termination to the hardwiring end cap (part 
number 870-70803). 
5. Attach the hardwiring end cap assembly to the power inlet end of 
the Rack PDU, using two of the screws removed in step 1. 
Note
Make sure that power to the Rack PDU has been turned 
off, and unplug any attached equipment to prevent damage 
if a mistake occurs during wiring.