FS-RA-CLX_SlotServer_Instruction_Manual_(T17011)   
 
 
Page 16 of 34 
 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldServer.com 
Tel: (408) 262-2299   Fax: (408) 262-2296   Toll_Free: 888-509-1970   email: support@fieldServer.com 
7.2. 
Step 2: Add and configure the SlotServer as an IO Module 
•  Right-click on I/O Configuration and select “New Module”. 
•  Choose the 1756-MODULE 
 
 
 
 
 
Choose 
the 
1756-MODULE 
Be  sure  to  choose  the  correct 
Slot  number  in  the  rack  where 
your SlotServer reside 
Click  Next  and  choose  a  RPI  of  100  ms. 
This is the rate at  which the I/O image data 
will be transferred