Appendix A.5.  Installing SlotServer on a Remote Rack using CNB Cards 
Appendix A.5.1. 
Hardware and Software requirements 
In order to perform this application, the following hardware and software is required as a 
minimum: 
 
•  At  least  two  1756  racks,  where  one  rack  contains  the  CPU  and  the  other  rack 
contains the SlotServer 
•  Two Controlnet CNB cards (with cable for connection) to connect the racks to each 
other 
•  RSlinx 
•  RSLogix 
•  RSNetworx 
•  SlotServer EDS file (Available on SlotServer CD, or call Technical Support) 
Note  that  it  is  possible  to  connect  to  SlotServer  on  a  remote  rack  using  other  1756 
bridging  cards.  This  chapter  only  deals  with  CNB,  but  the  principles  for  using  other 
bridging cards are similar. 
Appendix A.5.2. 
Setup 
•  Install the CPU and the first CNB card in the local rack. 
•  Install the second CNB card and the SlotServer in the remote rack. 
•  Connect the ControlNet Network 
•  Power up the racks 
•  Install the SlotServer EDS File using the RSLinx Hardware EDS Installation Tool. 
•  Make sure the SlotServer has a valid configuration loaded. The default configuration 
shipped with the SlotServer should suffice. 
Appendix A.5.3. 
RSLogix configuration 
In  order  to  see  the  SlotServer  from  the  CPU,  the  Hardware  must  be  configured  in 
RSLogix as follows: 
•  Configure  the  cards  in  the  local  rack  in  the  I/O  Configuration  section,  including  the 
CPU and the local CNB card. 
•  Right  click  on  the  local  CNB  card  and  add  the  remote  CNB  card  using  the  “New 
Module” function. 
•  Right Click on the remote CNB card, and add the 1756 Backplane 
•  Right Click on the 1756 Backplane and add the cards that are present in the remote 
rack, including the SlotServer (As a generic I/O module-see earlier section on how to 
do this) 
•  Save the RSLogix configuration, and download it to the PLC. 
 
The finished I/O configuration should look similar to this: