Appendix A.5.5. 
Testing 
The SlotServer should now be  visible to the CPU.  Go Online with RSLogix and check 
the Input buffer of the SlotServer for data.  A good check is to examine  offset 2 of the 
input tag for a non-Zero value.  If the SlotServer is multiplexing (DA_Count >1), then this 
value will be cycling through the Buffer numbers, otherwise if DA_Count=1, then offset 2 
will be fixed at 1.  If offset 2 is zero, then the SlotServer is not being seen by the CPU, 
and Diagnostics will need to be performed using RSNetWorx and RSLogix to determine 
the cause of the problem.