TP/FT10 LonWorks connection 
This  two  wire  connection  is  polarity  insensitive  and  can  be  multi-dropped  into  a  LonWorks 
Network. 
 
Ethernet Port 
The Ethernet port can be used for configuration and troubleshooting, as well as for Protocols 
that require an Ethernet connection.  Use standard Ethernet cables for this connection. 
 
RS-485 Port 
This is a standard 2-wire RS-485 port.  Specify as R1 in the configuration. 
 
4.2. 
Inside Cover Door Label 
A  label  has  been  provided  on  the  inside  of  the  cover  door  for  the  User  to  document 
important or useful configuration parameters used.  In particular, special provision has been 
made  to  document  the  Ethernet  port  IP  parameters,  as  well  as  the  LonWorks  DSN 
(Domain/Subnet/Node)  allocated  by  the  Network  Manager.    These  fields  are  there  to  be 
utilized at the User’s discretion. 
 
4.3. 
Technical Specifications 
Slot width 
BackPlane Current Load 
0.6A 
Operating Temperature 
0-60 Deg C (32-140 Deg F) 
Storage Temperature 
-40 – 85 Deg C (-40 – 185 Deg F) 
Humidity 
5-95% (Non-Condensing) 
Allen Bradley Platform: 
ControlLogix 1756 Rack 
LonWorks Connection type: 
TP/FT-10 
Ethernet port 
10/100 MB/sec. 
RS-485 port 
2-wire, half duplex. 
Approvals
1
 
UL 60950-1:2003 
CAN/CSA-C22.2 No.60950-1-03 
 
 
                                                 
1
 Refer to Error! Reference source not found. to view Certificates.