6. 
Configuring the CPU interface to the SlotServer 
6.1. 
CPU interface Description  
The SlotServer Data Images (Data Arrays) share data with the ControlLogix CPU tags using 
the backplane for communication and the FieldServer Logix driver.  To map the Logix Driver, 
the  Driver  needs  to  be  configured  in  the  SlotServer  Configuration.    The  information  that 
follows details the configuration parameters that can be used for this driver.  The driver can 
only act as an I/O Server (Adapter) to a Control-Logix CPU. 
Max Nodes Supported 
SlotServer Mode 
Nodes 
Comments 
Server 
Only one IO image connection supported 
 
6.2. 
Configuring the SlotServer as a Logix I/O Server 
For  a  detailed  discussion  on  SlotServer  configuration,  please  refer  to  the  FieldServer 
Configuration  Manual.    The  information  that  follows  describes  how  to  expand  upon  the 
factory  defaults  provided  in  the  configuration  files  included  with  the  SlotServer  (See  “.csv” 
sample files provided with the SlotServer). 
 
The  configuration  file  tells  the  SlotServer  about  its  interfaces,  and  the  routing  of  data 
required.    In  order  to  enable  the  SlotServer  for  Logix  communications,  the  driver 
independent  SlotServer  buffers  need  to  be  declared  in  the  “Data  Arrays”  section,  the 
SlotServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the 
data to be provided to the Clients needs to be mapped in the “Server Side Map Descriptors” 
section.  Details on how to do this can be found below. 
Note that in the tables, * indicates an optional parameter, with the bold legal value being the 
default. 
 
6.3. 
Data Arrays/Descriptors 
The  configuration  file  tells  the  SlotServer  about  its  interfaces,  and  the  routing  of  data 
required.    In  order  to  enable  the  SlotServer  for  Logix  communications,  the  driver 
independent SlotServer buffers need to be declared in the “Data Arrays” section. 
Section Title 
Data_Arrays 
Column Title 
Function 
Legal Values 
Data_Array_Name 
Provide name for Data Array 
Up  to  15  alphanumeric 
characters 
Data_Array_Format 
Provide  data  format.  Each  Data  Array 
can only take on one format. 
Float,  Bit,  UInt16,  SInt16, 
Packed_Bit, 
Byte, 
Packed_Byte, 
Swapped_Byte 
Data_Array_Length 
Number  of  Data  Objects.  Must  be 
larger  than  the  data  storage  area 
required  by  the  Map  Descriptors  for 
the data being placed in this array. 
For IO_Data_Type: 
REAL     1-120 
INT         1-244 
SINT       1-492 
DINT       1-120