4.2. 
Client Side Connection Descriptions 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Port 
Specify which port the device is connected 
to the FieldServer 
P1-P8
1
 
Protocol 
Specify protocol used 
SCS-128 
SCS128 
Safetran SCS-128 
Baud* 
Specify baud rate 
75,  150,  300  ,600,  1200,  2400,  9600 
(Vendor limitation) 
Parity* 
Specify parity 
Even (Vendor limitation) 
Data_Bits* 
Specify data bits 
8 (Vendor limitation) 
Stop_Bits* 
Specify stop bits 
1 (Vendor limitation) 
Handshaking*  Specify hardware handshaking 
None 
Poll_Delay* 
Time between internal polls 
0-32000 seconds, 0.05 seconds 
 
Example 
 
//    
Client Side Connections 
 
Connections 
Port, 
Protocol, 
Baud, 
Parity, 
Handshaking, 
Poll_Delay 
P8, 
SCS-128, 
9600, 
Even, 
 None, 
0.100s 
 
4.3. 
Client Side Node Descriptors 
Section Title 
Nodes 
Column Title 
Function 
Legal Values 
Node_Name 
Provide name for Node 
Up  to  32  alphanumeric 
characters 
Node_ID 
SCS-128 station address of physical Server Node 
1-127 
Protocol 
Specify protocol used 
SCS-128 
SCS128 
Safetran SCS-128 
Connection 
Specify  which  port  the  device  is  connected  to  the 
FieldServer 
P1-P8
1
 
SCS128_Ack* 
If ON, Ack will be sent to Server upon receipt of every 
indication response 
OFF, ON 
 
Example 
 
//    Client Side Nodes 
 
 
 
 
 
Nodes 
 
 
 
 
Node_Name, 
Node_ID, 
Protocol, 
Connection, 
SCS128_Ack 
NODE_A, 
1, 
SCS-128, 
P8, 
OFF 
 
                                                 
1
 