and  answering  conditions  in  each  box  encountered,  until  a  problem  and/or  the  repair  is  explained.    After  any 
maintenance  or  repair,  the  trouble  shooting  sequence  should  be  repeated  until  the  trouble  shooting  procedure  ends 
with a normal system operation. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
S86 CHECKOUT AND TROUBLE SHOOTING 
 
START 
NOTE:  Before troubleshooting, familiarize yourself 
with the startup and checkout procedure.
 
TURN GAS SUPPLY OFF.  
TURN THERMOSTAT 
(CONTROLLER) TO CALL 
FOR HEAT 
POWER TO MODULE (24v 
NOMINAL)
 
Check line voltage power, low voltage transformer, limit controller, thermostat 
(controller) and wiring. 
 
SPARK ACROSS 
IGNITOR/SENSOR GAP
 
Pull ignition lead and 
check spark at module. 
 
Spark okay?
 
 
On models with vent damper plug, make sure vent 
damper had not been installed, then remove.  
Replace vent damper if necessary.
 
 
On other models, replace module.
 
 
Check ignition cable, ground wiring, ceramic insulator and gap, and correct.
 
 
Check boot of the ignition cable for signs of melting or buckling.  Take protective 
action to shield cable and boot from excessive temperature.
 
TURN GAS SUPPLY ON 
 
 
PILOT BURNER LIGHTS?
 
 
Check that all manual gas valves are open, supply tubing and  pressure are good, 
and pilot burner orifice is not blocked.
 
 
Check electrical connections between module and pilot operator on  gas control.
 
 
Check for 24 Vac across PV-MV\PV terminals on module.  If voltage is okay, 
replace gas control; if not, replace module.
 
SPARK STOPS WHEN 
PILOT IS LIT?
 
NOTE:  If S8600B,H; S8610B, H goes into lockout, reset system.  For S8600M, 
wait 6 minutes nominal for retry or reset system. 
 
Check continuity of ignition cable to ground wire. 
 
Clean flame rod. 
 
Check electrical connection between flame rod and module. 
 
Check for cracked ceramic flame rod insulator. 
 
Check that pilot flame covers rod and is steady and blue. 
 
Adjust pilot flame. 
 
If problem persists, replace module.
 
MAIN BURNER 
LIGHTS?
 
 
Check for 24 Vac across MV-MV\PV terminals.  If no voltage, replace module. 
 
Check electrical connections between module and gas control.  If okay, replace 
gas control or gas control operator.
 
SYSTEM RUNS UNTIL 
CALL FOR HEAT 
LOSS? 
NOTE:  If S8600B,H; S8610B, H goes into lockout, reset system.  For S8600M, 
wait 6 minutes nominal for retry or reset system. 
 
Check continuity of ignition cable and ground wire.  
NOTE:  If ground is poor or erratic, shutdowns may occur occasionally even 
though operation is normal at the time of checkout. 
 
Check that pilot flame covers flame rod and is steady and blue. 
 
If checks are okay, replace module.
 
CALL FOR HEAT ENDS 
SYSTEM SHUTS OFF?
 
 
Check for proper thermostat (controller) operation. 
 
Remove MV lead at module; if valve closes, recheck temperature controller and 
wiring; if not, replace gas control.
 
TROUBLESHOOTING 
ENDS
 
Repeat procedure until troublefree operation is obtained.
 