The safety lockout timer circuit starts timing the moment the trial for pilot ignition starts.  When the timing period runs 
out, the trial for ignition ends, and the control module goes into lockout.  Before another attempt to start can be made, 
the S86 must be reset.  Reset by adjusting the thermostat or controller or to its "OFF" position.  An alternate method is 
to  shut  the  system  power  "OFF".    If  normal  ignition  does  not  occur,  use  the  trouble  shooting  table  to  determine  the 
problem. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
SERVICE 
 
PRELIMINARY CHECK 
 
The following visual checks should be made before trouble shooting and after installation or maintenance. 
1. 
Check power to appliance and S86. 
2. 
Manual shutoff cocks in gas line to appliance must be open. 
3. 
Make certain all wiring connections are clean and tight. 
4. 
First de-energize the system and wait at least one (1) minute.  This resets the module allowing a return to start 
condition.  Then energize the system. 
5. 
Review the S86 system normal sequence of operation. 
 
SYSTEM TROUBLE SHOOTING 
 
Start  the  system  by  setting  the  thermostat  or  controller  above  required  temperature.    Observe  system  response.  
Establish  type  of  malfunction  or  deviation  from  normal  operation.    Use  the  S86  Intermittent  Pilot  System  Trouble 
Shooting Table  to check for normal system operation. 
 
Use table by following instruction questions in box.  If the condition is true or okay (answer yes), go down to next box 
underneath.  If the condition is not true or not okay (answer no), go right to the next box alongside.  Continue checking 
2
2
2
2
   SPARK GENERATOR POWERED 
 
First valve (pilot) operator opens 
3
3
3
3
  PILOT BURNER OPERATION 
Pilot burner lights. 
Module senses flame 
current. 
OR 
Pilot burner does not light. 
After 90 second
system 
locks out; must be manually 
reset. 
a
 Shutoff/lockout timing is stamped on module. 
4
4
4
4
  FLAME CURRENT SENSED 
 
Spark generator off. 
 
Second valve operation (main) opens. 
5
5
5
5
 
MAIN BURNER OPERATION 
Module monitors pilot flame current. 
6
6
6
6
  THERMOSTAT (CONTROLLER) SATISFIED 
 
 
Valves close, pilot and main burners are off. 
1
1
1
1
  
THERMOSTAT (CONTROLLER) CALLS 
FOR HEAT
 
POWER INTERRUPTION 
System shuts off, restarts 
when power is restored. 
 
PILOT FLAME FAILURE 
Main valve closed. 
Module starts trial for ignition.
 
START 
STAGE 1 
TRIAL FOR 
IGNITION 
STAGE 2 
MAIN BURNER 
OPERATION 
END