Closed circuit cooler selections can easily be made by using the information on pages 6 through 11. The 
examples below demonstrate proper procedures for water and ethylene glycol solutions. Other fluids can be 
cooled, but since their heat transfer and flow characteristics may vary, please contact your local Recold sales 
representative for assistance.
WATER SELECTION EXAMPLE
Select a unit to cool 225 GPM of water from 102°F to 
90°F at 76°F wet bulb temperature.
1.  Determine Range:
  102°F - 90°F = 12°F Range
2. Determine Approach:
  90°F - 76°F = 14°F Approach
3.  Select Load Factor — 
Enter Unit Load Factor Table 2  
for 76°F wet bulb. Select load factor based on 
12°F range and 14°F approach. Load factor in this 
example equals 3.3. When wet bulb temperature 
is an odd number interpolate between appropriate 
tables to determine the load factor.
4.  Select Unit Model — 
Table 3, the load factor 
determined in step 3 falls between 3.0 and 3.5. 
Enter the 3.0 column and read down to the smallest 
unit flow rating which is greater than or equal to 
225 GPM. For the Model JWL35B, interpolate 
between 245 and 190 GPM to determine the 
flow rating at the 3.3 load factor. Interpolation 
gives a rating of 212 GPM which is less than the 
design requirement. Select a Model JWL35C and 
again interpolate between load factor columns 
to determine flow rating. The second selection 
provides a flow rating of 245 GPM which exceeds 
the design requirement. The correct unit size is, 
therefore, a Model 35C
5.  Determine Flow Limitations — 
Enter Table 3 at unit 
size determined in Step 4 to select a JWL low flow 
or JW standard flow unit. The Model 35C with 225 
GPM design flow falls within the standard coil flow 
limitations. The correct unit selection is, therefore, 
a JW35C.
6.  Determine Coil Pressure Drop — 
Enter the Coil 
Pressure Drop Table at 225 GPM and read across 
to the unit model column to select pressure drop 
reading. In this example, pressure drop equals  
4.8 PSI.
ETHYLENE GLYCOL EXAMPLE
Select a unit to cool 75 GPM of 40% by volume 
ethylene glycol from 107°F to 85°F with 78°F wet 
bulb.
1. Determine Range:
  107°F - 85°F = 22°F Range
2. Determine Approach:
  85°F - 78°F = 7°F Approach
3.  Select Load Factor — 
Enter Table 2 for 78°F wet bulb 
and select load factor at design range and approach. 
Select 6.0 factor.
4.  Select Test Unit Model — 
Enter the Unit Rating 
Table 3 at the 6.0 load factor and read down to the 
smallest unit flow rating greater than or equal to the 
design 75 GPM. Select the test model JWL35C
5.  Correct Flow for Ethylene Glycol — 
The flow correction 
factor obtained from Table 1 is 1.04. 75 GPM x 1.04 
= 78 GPM
6.  Adjust Model Selection — 
Re-enter Table 3 at the 6.0 
load factor and make selection based on corrected 
flow of 78 GPM. The adjusted unit selection is the 
Model JWL50A indicating an 80 GPM rating
7.  Determine Flow Limitations — 
Enter Table 3 at unit 
size determined in Step 6 to select a JWL low flow 
or JW standard flow unit. The Model 50A with 
75 GPM design flow falls within the low flow coil 
limitations. The correct unit selection is, therefore, 
a JWL50A.
8.  Determine Coil Pressure Drop — 
For ethylene glycol 
pressure drop calculation, the conversion factor 
from Table 5 must be applied to design flow before 
entering Table 4. 75 GPM x 1.05 = 79 GPM. 
The coil pressure drop for 79 GPM is 2.4 PSI
DEFINITIONS
Range: the difference between the entering and 
leaving water temperatures (WT in – WT out).
Approach: the difference between the leaving water 
temperature and the web bulb temperature (WT out 
– WB).
Load BTUH =
GPM x 500 x Sp. Gr. x Sp. Ht. x (T
1
 – T
2
) where
Sp. Gr. = specific gravity at average temperature
Sp. Ht. = specific heat at average temperature
T
1
 = entering temperature
T
2
 = leaving temperature