InSinkErator AS-101K 用户手册

下载
页码 12
6
PERSONAL INJURY
 • Allow only trained personnel to operate disposer.
 • Use baffles and guarding to avoid splashing and 
ejection of materials.
 • Do not put fingers or hands into the disposer.
 • When attempting to remove objects from a  
disposer, use long-handled tongs or pliers.
 • Turn power off before clearing a jam, removing an 
object from the disposer or pressing the red reset 
button. (See Troubleshooting).
 • Disconnect electricity before adjusting set points.
ELECTRIC SHOCK
 • Turn off the electrical supply to the disposer before  
  attempting any work on it. Use a voltmeter or  
  circuit tester to ensure that power is off.
 • All installation work must conform to local  
plumbing and electrical codes.
 • All control centers and disposers must be carefully 
and permanently grounded.
 • A properly fused disconnect must be installed at 
the electrical supply source for the control center.
• The control center’s door disconnect must be in the 
off position before the panel door can be opened.
Power is still present at the disconnect until power 
is turned off at the electrical supply source. 
LINE VOLTAGE
Connect the incoming line power to the electrical 
disconnect switch and connect the disposer motor to 
labeled terminal blocks in the control center. Use the 
appropriate voltage and phase electrical connection 
diagram, Figure 3, 4, 5, or 6.
LOW VOLTAGE
The AS-101K control center uses low voltage (24 V)  
to operate contactor coils, solid state control circuit, 
push buttons, and solenoid valves. Red wires denote  
a 24 V circuit.
REMOTE CONTROL STATION
Any number of remote control stations can be used. 
Mount remote controls within sight of the disposer  
per local codes. Refer to Figure 7. 
Remove jumper 
wire between #2 and #3 when using remote  
control station.
Figure 7. Remote Control Station Wiring
24V Water Solenoid
1 GPM Flow Control
24V Water Solenoid
7 GPM Flow Control
Stop
Start
Multiple
Remote
Start
(N.O.)
Multiple
Remote
Stop
(N.C.)
Jumper Wire
Removed
For Remote
Operation
2
3
4
6
7
7
13
Disposer
14
Figure 7. Remote Control Station Wiring
WATER SOLENOID VALVE
Two 24 V solenoid valves are supplied with all control 
centers. Connect one 24 V solenoid valve (in line with 
the 1 GPM flow control) to terminal 4 and 13, connect 
the other 24 V solenoid valve (in line with the 7 GPM 
flow control) to terminal 4 and 14. See Figure 7.
Wire per local electrical code using 7/8" diameter holes 
in bottom of control center cabinet and install NEMA 4 
water-tight electrical connectors.
After completing the connections, replace all terminal 
block shields, close door, and fasten all locking clamps. 
Replace disposer motor cover. Turn on power.
Please read the disposer operating instructions and 
train your personnel before operating the disposer.  
The operating instructions include:
• Disposer operation
• How to restart the disposer after a jam condition
PROPERTY DAMAGE
 •  Ensure that control center voltage and phase 
match the disposer motor and electrical supply. 
Check name plates on disposer and control  
centers for voltage and phase specifications.
 • Refer to the control center wiring diagrams in this 
manual for correct connection.
 • Use NEMA 4 watertight electrical connectors  
(not supplied) when making electrical connections 
to the control center.
Electrical Connections