g) Freeze Timer (S4 dip switch 9 & 10)
CAUTION
Adjust to proper specification, or the unit may not operate correctly.
The freeze timer setting determines the maximum allowed freeze time to prevent 
possible freeze-up issues. Upon termination of the freeze timer, the control board 
initiates the harvest cycle. After  consecutive freeze timer terminations, the control 
board shuts down the icemaker. In this case, see "IV.F.3. Low Ice Production" for 
possible solutions. The freeze timer is factory set, and generally no adjustment 
is required. Before changing this setting, contact Hoshizaki Technical Support at 
-800-33-940 for recommendations.
S4 Dip Switch Setting
Time 
(minutes)
No. 9
No. 10
OFF
OFF
60
OFF
ON
50
ON
OFF
70
ON
ON
60
h) Float Switch Control (S5 dip switch 1): "G" Control Board 
CAUTION
Do not adjust. This must be left in the factory default position or the unit will not 
operate correctly.
Factory set. S5 dip switch  allows for single or double float switch applications. The 
KM-90MAH, KM-90MWH, and KM-90MRH/3 use a single float switch.
i) Refill Counter (S5 dip switch 2 through 5): "G" Control Board
CAUTION
Do not adjust. These must be left in the factory default position or the unit will 
not operate correctly.
Factory set. S5 dip switch  through 5 allows for refills during the freeze cycle. The 
KM-90MAH, KM90MWH, and KM-90MRH/3 do not refill.