Appendix B
Cabling Requirements
Getting Started with CAN for Windows NT
B-6
©
 National Instruments Corporation
Maximum Number of Devices
The maximum number of devices that you can connect to a CAN port 
depends on the electrical characteristics of the devices on the network. If all 
of the devices meet the requirements of ISO 11898, at least 30 devices may 
be connected to the bus. Higher numbers of devices may be connected if the 
electrical characteristics of the devices do not degrade signal quality below 
ISO 11898 signal level specifications. If all of the devices on the network 
meet the DeviceNet specifications, 64 devices may be connected to the 
network.
Cable Termination
The pair of signal wires (CAN_H and CAN_L) constitutes a transmission 
line. If the transmission line is not terminated, each signal change on the 
line causes reflections that may cause communication failures.
Because communication flows both ways on the CAN bus, CAN requires 
that both ends of the cable be terminated. However, this requirement does 
not mean that every device should have a termination resistor. If multiple 
devices are placed along the cable, only the devices on the ends of the cable 
should have termination resistors. See Figure B-6 for an example of where 
termination resistors should be placed in a system with more than two 
devices.
Figure B-6.  Termination Resistor Placement
The termination resistors on a cable should match the nominal impedance 
of the cable. ISO 11898 requires a cable with a nominal impedance of 
120
Ω
; therefore, a 120
 
Ω
 resistor should be used at each end of the cable. 
Each termination resistor should each be capable of dissipating 0.25 W of 
power.