National Instruments cFP-PWM-520 用户手册

下载
页码 19
FP-PWM-520 and cFP-PWM-520
4
ni.com
Wiring the [c]FP-PWM-520
The FP-TB-x terminal base has connections for each of the eight 
output channels and for an external power supply to power the 
output channels and field devices. The cFP-CB-x connector block 
provides the same connections. Each channel has one output 
terminal (V
OUT
), one supply terminal (V
SUP
), and two common 
terminals (COM). All eight channels are referenced to the COM 
terminals. The V and V
SUP
 terminals are all internally connected, 
as are the C and COM terminals.
Table 1 lists the terminal assignments for the signals of each 
channel. Terminal assignments are also listed on the side panel 
of the cFP-PWM-520 and under the slide-in card on the front of the 
FP-PWM-520. Connect to the terminals using the terminal base, 
connector block, or other connectivity accessory.
Use a 5 VDC or 10–30 VDC external power supply for the output 
channels. The power supply must provide enough current to power 
all of the loads on the output channels, up to a maximum of 1 A per 
channel. Connect the external power supply to multiple V and V
SUP
 
terminals and to multiple C and COM terminals as needed to 
ensure that the maximum current through any terminal is 2 A 
or less.
Table 1.  Terminal Assignments
Channel
Terminal Numbers
V
OUT
*
V
SUP
COM
0
1
17
2, 18
1
3
19
4, 20
2
5
21
6, 22
3
7
23
8, 24
4
9
25
10, 26
5
11
27
12, 28
6
13
29
14, 30
7
15
31
16, 32
*
 Install a 1 A maximum, fast-acting fuse on each V
OUT
 terminal.
 Install a 2 A maximum, fast-acting fuse on each V
SUP
 terminal.