Rosslare Enterprises Ltd AYCF6X 用户手册

下载
页码 66
Installation 
AYC-F/G/M60 Series Installation and Programming Manual 
15 
5.
  Trim and cover all conductors that are not used. 
 
  The individual wires extending from the reader are color-coded 
according to the required Wiegand standard. 
  When using a separate power supply for the reader, this supply and 
the controller’s power supply must have a common ground. A linear 
power supply is recommended. 
  Attach the cable shield wire on the reader to an earth ground (best), 
or to a signal ground connection at the panel or power supply end of 
the cable. This configuration is best for shielding the reader cable from 
external interference. 
3.2.2
 
Wiring the Unit as a Controller 
If you connect the unit to a Rosslare PS-x25x secured power supply, it 
automatically functions as a controller. 
To connect the unit as a controller: 
1.
  Select the appropriate connections according to Table 2. 
Table 2: Wiring the Unit as a Controller 
Controller  Wire Color  Function 
Note 
Red 
+DC Input 
Wired to the PS-x25x 
Black 
Ground 
Wired to the PS-x25x 
C 1 
White 
Communication 
Wired to the PS-x25x 
C 2 
Green 
Communication 
Wired to the PS-x25x 
AUX. IN 
Brown 
Auxiliary Input 
Wired to input 
N/A
 
Purple 
Not in use 
N/A 
 
 
Attach the cable shield wire on the unit to an earth ground (best). 
You can also attach it to a signal ground connection at the panel or 
power supply end of the cable. This configuration is best for 
shielding the controller cable from external interference. 
2.
  Prepare the PS-x25x secured power supply’s cable by cutting the 
cable jacket back 3.2 cm (1¼”) and strip the wire 1.3 cm (½”). 
3.
  Splice the controller pigtail wires to the corresponding PS-x25x 
secured power supply’s wires and cover each joint with insulating 
tape.