Chauvin Arnoux P01120073Clip-on ammeter adapter 39 mm P01120073 用户手册

产品代码
P01120073
下载
页码 72
17
3.5/ AUTO OFF
The PAC 22 has an Auto Off feature which switches approximately 10 minutes after the clamp
has been switched on.  Any operation of the switch or the auto zero button reinitialises the
Auto Off function.
When the clamp is switched off by this automatic function, the switch 
 must first be set to
the OFF position before being switched on again.
This function can be overridden by the user when switching on. Simply press the auto zero
button 
 at the same time as setting the switch 
 from the OFF position to the 1 mV/A or 10
mV/A position.
If the green indicator 
 flashes whilst the zero reset button is being pressed, this indicates
that the auto off function has been inhibited.
4.1/ RÉFERENCE CONDITIONS
- Temperature: 18...28°C
- Humidity rate: 20...75% RH
- Battery voltage: 9 V ± 0.1 V
- Position of conductor: centred on the markings of the clamp
- Magnetic field: earth’s DC field
- Absence of external AC magnetic field
- Absence of electric field
- Measurement for a DC current or an AC sinusoidal current 
 65 Hz
- Impedance of the measurement instrument: 
 1 M
Ω
 and 
 100 pF
Ranges
Input/output ratio
Measurement extent
A AC rms
A peak max
A DC
100 A
10 mV/A
0.2...100
0.2...150
0.4...150
1000 A
1 mV/A
0.5...1000
0.5...1400
0.5...1400
4/ SPECIFICATIONS