2. Hints
  
 
2.7 Auto-tune (self-setting function)
 
 
 RWF40 user manual section 6.2.4 and 9.1 
 
The RWF40 User manual refers to a ‘self-setting-function’  
that for the purposes of this manual will be refered to as ‘Auto-tune’. 
 
 
Technical Explanation 
 
Auto-tune is a self-setting software function,  
that is integrated into the RWF40 controller,  
and can be repeated as often as desired. 
 
Auto-tune tests the reaction, in the modulating mode of operation,  
of the process-control loop, to steps in the actuator position,  
according to a special procedure. 
 
The data, during the forced oscillations, is then recorded, and used to 
calculate new values, that are optimized for your specific controlled 
system. 
 
Auto-tune items summary:
 
 
 
Values for 
Pb.1
dt, rt
 and
 dF1
, can always be changed. 
 
Auto-tune
 uses two different methods to force oscillations,  
and will automatically select and use, a method, based on,  
at the start of Auto-tune, what the difference is,  
between the setpoint (w), and the 
process value
 
When Auto-tune is started with a large difference
(typically before the process-control loop has stabilized)  
Auto-tune performs a forced oscillation around a 
switching level
.  
 
When Auto-tune is started with a small difference
(typically after the process-control loop has stabilized)  
Auto-tune performs a forced oscillation, around the setpoint (w)
 
 
 
 
 
 
 
 
 
 
 
 
 
 
If for any reason the controller exceeds the switch off threshold (HYS3)  
Auto-tune will be cancelled. 
Conditions
 
 
The controller must be : 
 
- in the modulating output mode (D1 is open and the step icon
 is off) 
 
- burner is released (green LED  above 
 
is on, relay 1, is activated,  
contact between terminals Q14 and Q13 is closed) 
 
- controller is not in manual mode (red LED  above 
 
is off) 
 
 
Procedure
 
 
Start Auto-tune by pressing 
 
and release. 
 
The current temperature value, (
175
)  
is shown in the actual value display. 
 
The current function item (
tunE
)  
is flashing in the setpoint display. 
 
You can cancel Auto-tune while it is flashing 
pressing 
 and releasing. 
 
 
 
 
 
When  tunE stops flashing on it’s own 
Auto-tune is complete. 
 
You can save the new values for 
Pb.1
dt, rt
 and
 dF1
by pressing 
and holding for at least 2 seconds. 
 
 
 
 
 
Possible results,and their correction. A favorable value for dt is rt/4. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Block diagram of Auto-tune. 
Items at the user level that will affect Auto tune 
SP 1 
S
et
 P
oint
 1 
 
HYS1 
Switch-on threshold, 
HYS
teresis 
1
 
 
HYS3 
Switch-off threshold, 
HYS
teresis 
3
,  
 
 
Items at the Parameter level that Auto-tune will adjust 
Pb.1 P
roportional 
b
and 
1
 
(Factory setting  10) 
dt d
erivative
 t
ime 
(Factory setting  80) 
rt 
Integ
r
al action
 t
ime
 
(Factory setting  350)
 
 
 
Item at the configuration level that Auto-tune will adjust 
dF1 
Time constant for 
d
igital 
F
ilter, analog 
1