Siemens RWF40 用户手册

下载
页码 15
6/16                              CC1B-Hints-en 
Preliminary
                                 04.02.2003                                        HVAC Products 
2. Hints 
 
2.5 How to display the software version and 
units
 
 
 RWF40 user manual Section 6.2 .5
 
 
 
Shown at the right is the basic display. 
 
 
 The current configuration of your specific 
controller will determine which levels you will  
be allowed to access. 
 
A C112 of xxx3 will prevent use of the keys. 
 
 
The C112 locking code can only be adjusted  by the manufacturer. 
 
 
You can display the software version, and units, of your controller,at any 
time, by pressing the  
 
  at the same time,and holding them… 
 
You will see one, of the three displays shown below.
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The software version of your controller, (Version 
102
 in this example.) is 
shown in the actual value display. 
 
The current units configuration ( 
ºC
,
 ºF
, or
  %
) is shown in the setpoint 
display. 
  
 
The display will return, to the where it was, if you release the keys at 
the same time, if not, you will return back to the basic display. 
 
 
Configure Codes \ Units summary: 
 
 
ºC will be displayed if your controller is configured with: 
 
 
 
 
C111 
0xxx .. dxxx 
Analog input 1  
Sensor (Pt100, Ni100, .. ) 
C113 
xx0x No 
decimals 
ºC 
C113 
xx1x One 
decimal 
ºC  
 
 
 
 
ºF will be displayed if your controller is configured with 
C111 
0xxx .. dxxx 
Analog input 1 
Sensor (Pt100, Ni100, .. ) 
C113 
xx2x 
No decimals 
ºF 
C113 
xx3x 
One decimal 
ºF 
 
 
 
 
% w ill be displayed if your controller is configured with: 
C111 
Exxx .. Hxxx 
Analog input 1 
Standard input (4-20mA, .. ) 
C113 
xx0x ..  xx3x 
 
Doesn’t matter 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
2.6 Manual operation
 
 
 RWF40 user manual Section 6.2 .2 and 6.2.3.
 
 
 
Shown at the right is the basic display. 
 
 
 The current configuration of your specific 
controller will determine which levels you will  
be allowed to access. 
 
A C112 of xxx3 will prevent use of the keys. 
 
 
 
 
The C112 locking code can only be adjusted  by the manufacturer. 
 
 
 
 
 
Manual operation can only be performed  
when the thermostat function is active  
and burner is released to modulation. 
 
The 
green
 burner LED must be on,  
relay 1 is energized, and the contact,  
Q13 N.O. - Q14 Com, is closed.   
 
If at any time the burner LED turns off, the 
controller will exit the manual operation function.