Modulating burner, 3-Position output   
 
Press 
 and hold for 5 seconds, and release. 
 
The 
red
 LED above the manual icon turns  
on to indicate that the controller is now in the  
manual mode. 
 
Relay 2 and relay 3 will hold their current state, 
(energized or de-energized) that they were in until  
another key is pressed. 
 
 
 
 
 
 
 
When the 
 When 
the 
  
is pressed: 
is released: 
-Relay 3 is 
-Relay 3 is 
energized 
de-energized 
-Decrease icon 
-Decrease icon 
turns on 
turns off 
-N.O. contact Q-Y2 
-N.O. contact Q-Y2 
closes, to drive the 
opens, to hold the 
modulating device 
modulating device 
down, which 
where it is, which 
decreases the 
holds the 
firing rate 
firing rate  
of the burner.  
of the burner. 
 
 
 
 
When the 
 When 
the 
  
is pressed:  
is released: 
-Relay 2 is 
-Relay 2 is 
energized 
de-energized 
-Increase icon 
-Increase icon 
turns on 
turns off 
-N.O. contact Q-Y1 
-N.O. contact Q-Y1 
closes, to drive the 
opens, to hold the 
modulating device 
modulating device 
up, which 
where it is, which 
increases the firing 
holds the firing 
rate of the burner. 
rate of the burner. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Modulating burner, Modulating output  
 
Press 
 and hold for 5 seconds, and release. 
 
The red LED above the manual icon turns  
on to indicate that the controller is now in the  
manual mode. 
 
Relay 2 and relay 3 will hold their current state, 
(energized or de-energized) that they were in until  
another key is pressed. 
 
 
 
By design, the 0 output starts driving the modulating device to low 
fire, but if you promptly press the 
 after the red LED above the hand 
icon turns on, you can prevent the from going all the way. 
 
 
When the 
  
When the 
 
is pressed,  
is released
the output value  
output value,  
starts increasing
stops increasing,  
and the output,  
and the output, 
to terminals  
to terminals  
X1+ and X1-  
X1+ and X1- also 
starts increasing
stops increasing,  
the same amount, 
and holds 
and increases 
the current 
the firing rate 
firing rate 
of the burner. 
of the burner. 
 
 
 
When the 
  
When the 
 
is pressed,  
is released
the output value  
output value,  
starts decreasing
stops decreasing,  
and the output,  
and the output, 
to terminals  
to terminals  
X1+ and X1-  
X1+ and X1- also 
starts decreasing
stops decreasing,  
the same amount, 
and holds 
and decreases 
the current 
the firing rate 
firing rate 
of the burner. 
of the burner. 
 
 
To exit manual operation 
 
 
Press 
 for 5 seconds, and release. 
 
The red LED above the hand symbol 
 turns off,  
and the controller returns to the automatic mode. 
 
 
On Modulating burners, with modulating output, 
 
the output to terminals X1 and X2, 
 
also returns to automatic operation.  
 
 
On Modulating burners, with 3-position output, 
 
the output to relay 2 and relay 3, 
 
also returns to   automatic operation.