2. Hints
  
 
2.4 How to change a setpoint 
 
(SP1, SP2, or dSP) 
 
 
 RWF40 user manual Section 6.2 
 
 
Shown at the right is the basic display. 
 
 The current configuration of your specific 
controller will determine which levels you will be  
allowed to access. 
 
 
C112 must be xxx2, xxx1, or xxx0 to access the 
 
parameter level. 
 
 
 
The C112 locking code can only be adjusted by the manufacturer. 
 
 
 
From the basic display, you may skip the  
user level, to reach the parameter level. 
 
Press  
 and hold, for 3 seconds,  
and release. 
 
The actual value display, (
0
shows the current parameter value. 
 
The setpoint display, (
AL
shows the parameter item you are adjusting.  
 
 
 
Parameter level items summary:
 
 
 
 
* items are only displayed when 
 
  controller is configured for 3-pos output. 
Example    Adjust the value for parameter AL. 
 
 If no keys are pressed for 30 seconds, at anytime, the controller will 
automatically return to the basic display. 
 
 
The current value of AL, (
0
)  
is shown in the actual value display. 
 
The current parameter item (
AL
)  
is shown in the setpoint display. 
 
The display is steady, (nothing is flashing) 
and the value for AL can now be adjusted. 
 
 
 
 
 
 
 
You can   
You can 
decrease   
increase 
the value  
the value 
by pressing 
by pressing 
 and 
 and 
releasing it. 
releasing it. 
 
 
 
 
 
 
You can   
Or, you can 
accept the  
advance to  
change by    
the next  
waiting 2   
parameter  
seconds.    
by pressing  
 
 
 once 
The red  
and releasing it. 
LED’s will  
 
blink once, 
HYSt can be 
and become 
adjusted the 
the new 
same way you 
value. 
just did AL 
 
 
 
Your options at this point are: 
 
Press 
 
and release
,
 to immediately return to the basic display. 
 
Press 
 
and release it,  
to advance down to Pb.1,  (the next parameter). 
 
… after the last parameter item P, 
press 
 
and release it,  
to advance down to SP1, (the 1
st
 user item). 
 
… after the last user item, 
the menu cycles back to the 1
st
 user item. 
 
 
Or simply wait 30 seconds and the controller will automatically return to 
the basic display.
 
 
 
 
 
 
 
 
 
AL A
larm 
L
imit value for comparator
 
HYSt 
Switching differential, 
Hyst
eresis for limit comparator
 
Pb.1 P
roportional 
b
and 
1
 
dt d
erivative
 t
ime 
rt 
Integ
r
al action
 t
ime
 
db 
* 
d
ead 
b
and, contact spacing 
 
tt 
* Ac
t
uator running
 t
ime 
HYS1 
Switch-on threshold, 
HYS
teresis 
1
, 2-stage burner 
HYS2 
Switch-off threshold, 
HYS
teresis 
2
, 2-stage burner 
HYS3 
Switch-off threshold, 
HYS
teresis 
3
, upper 
Response threshold 
H H
eating curve slope 
P P
arallel displacement